7. Specification
MODEL 1KVA(S) 1.5KVA(S) 2KVA(S) 3KVA(S)
PHASE Single phase with ground
Capacity (VA/Watts)
1000 VA /
1000 W
1500 VA /
1500 W
2000 VA /
2000 W
3000 VA /
3000W
INPUT
Nominal voltage 208/220/230/240VAC
Operating
voltage range
(Ambient
Temp.
<40 °C)
Low line
transfer
176 Vac ± 5 % @ 100 % - 50 % load;
110 Vac ± 5 % @ 50 % - 0 % load;
Low line
comeback
186 Vac ± 5 % @ 100 % - 50 % load;
120 Vac ± 5 % @ 50 % - 0 % load;
High line
transfer
264 Vac ± 5 % @ 100 % - 50 % load;
300 Vac ± 5 % @ 50 % - 0 % load;
High line
comeback
254 Vac ±5 % @ 100 % - 50 % load;
290Vac ± 5 % @ 50 % - 0 % load;
Operating frequency
range**
40 70 Hz
Power factor 0.99 @ 100 % load (Nominal Input Voltage)
Bypass voltage range
Bypass high voltage point
230-264: setting the high voltage point in LCD from
230 Vac to 264 Vac. (Default: 264 Vac)
Bypass low voltage point
170-220: setting the low voltage point in LCD from 170
Vac to 220 Vac. (Default: 170 Vac)
Generator input Support
OUTPUT
Output voltage* 208/220/230/240 Vac
Power factor 1.0
Voltage regulation ±1 %
Frequency
Line Mode
(synchroni
zed range)
46-54 Hz or 56-64 Hz
Bat. Mode
(50/60±0.1) Hz
Crest factor 3:1
Harmonic distortion (THDv)
3 % THD with linear load
5 % THD with non linear load