DL9110 / DL9118 Operating Instructions
- 30 -
6.4 Line Impedance
Supply Voltage 195V – 253V, 45Hz – 65Hz
328V - 440V, 45Hz – 65Hz
Nominal Test Current 3A
Display Range
0.01Ω - 2000Ω
Measuring Range
0.1Ω - 1999Ω
Resolution
0.01Ω maximum
Accuracy ±5% ±5 digits
PFC Range 0kA – 26kA
6.5 RCD
Supply Voltage 195V – 253V, 45Hz – 65Hz
Nominal Test Currents 10mA, 30mA, 100mA, 300mA,
500mA
Test Current Accuracy
-0% +10% at I∆n and 5I∆n
-10% +0% at ½ I∆n
Trip Time Ranges
0ms – 2000ms, ½ I∆n
0ms – 300ms, I∆n General
0ms – 500ms, I∆n Selective
0ms – 40ms, 5I∆n
Trip Time Accuracy ±5% ±2 digits
Ramp Current Range
½ I∆n to 1.1 I∆n
Trip Current Measurement
Accuracy
10%
6.6 Voltage/Frequency Measurement
Display Range 0V – 440V
Voltage Measuring Range 0V – 440V
Resolution 1V
Accuracy ±5% ±2 digits
Frequency Range 45Hz – 65Hz
Frequency Accuracy ±1Hz