Allure EC-Smart-Comfort Series
Product Description
The Allure EC-Smart-Comfort Series are versatile communicating sensors which provide precise temperature sensing.
Tailored for occupants, the Allure EC-Smart-Comfort Series' intuitive design features coloured LED indicators to provide user feedback, rotary knobs to
adjust the setpoint offset and fan speed, and a push-button to apply occupancy override.
As a multi-function room device, the Allure EC-Smart-Comfort Series sensor can be expanded with a combination of up to 4 Smart-Light/Blind Series
add-on push-button modules, for lighting and shade/sunblind control, making it an ideal all-in-one addition to the Smart Room Control solution.
This document describes the hardware installation procedures for the Allure EC-Smart-Comfort sensors. This line of communicating sensors is com-
posed of the following models:
£ Allure EC-Smart-Comfort-S
£ Allure EC-Smart-Comfort-S-DI
£ Allure EC-Smart-Comfort-SO
£ Allure EC-Smart-Comfort-SO-DI
£ Allure EC-Smart-Comfort-SF
£ Allure EC-Smart-Comfort-SF-DI
£ Allure EC-Smart-Comfort-SOF
£ Allure EC-Smart-Comfort-SOF-DI
This document also covers the installation of the Smart-Light/Blind Series add-on modules.
General Installation Requirements
For proper installation and subsequent operation of the device, pay special attention to the following recommendations:
£ It is recommended that the product(s) be kept at room temperature for at least 24 hours before installation to allow any condensation that may have
accumulated due to low temperature during shipping/storage to evaporate.
£ Upon unpacking the product, inspect the contents of the carton for shipping damages.
Do not install damaged modules
.
£ The device is designed to operate under such environmental conditions as specified in its datasheet.
£ Ensure proper ventilation of the device and avoid areas where corroding, deteriorating or explosive vapors, fumes or gases may be present.
£ Do not drop the device or subject it to physical shock.
£ If the device is used and/or installed in a manner not specified by Distech Controls, the functionality and the protection provided by the device may
be impaired.
£ To ensure reading accuracy, handle the sensor with care, and avoid installing it on a vibrating surface.
Make connections to the product last. Yanking the cable while it is attached to the product can damage the
connector.
Any type of modification to any Distech Controls product will void the product’s warranty.
Take reasonable precautions to prevent electrostatic discharges to the product when installing, servicing, or
operating it. Discharge any accumulated static electricity by touching a grounded object with your hand before
handling the product.
I n s t a l l a t i o n G u i d e
Question and Answer IconNeed help?

Do you have a question about the Distech Controls Allure EC-Smart-Comfort Series and is the answer not in the manual?

Summary

Product Description

General Installation Requirements

Device Markings

Device Dimensions

Mounting Instructions

Installation Procedure

Connectors and DIP Switch Location

Wiring the Allure EC-Smart-Comfort with a Digital Input Cable

Supported Quantity

About the Subnetwork Bus

Subnetwork Bus Topology and EOL Terminations

Setting the Allure EC-Smart-Comfort Sensor Subnet ID

Maintenance and Cleaning

FCC Statement

Overview

The Allure EC-Smart-Comfort Series comprises versatile communicating sensors designed for precise temperature sensing and enhanced occupant control within smart room environments. These devices are integral to a comprehensive Smart Room Control solution, offering a blend of intuitive design, user feedback, and expandability.

Function Description

At its core, the Allure EC-Smart-Comfort Series functions as a communicating sensor that accurately measures room temperature. It is designed to integrate seamlessly into building management systems, providing critical data for environmental control. The series supports various models, including:

  • Allure EC-Smart-Comfort-S
  • Allure EC-Smart-Comfort-S-DI
  • Allure EC-Smart-Comfort-SO
  • Allure EC-Smart-Comfort-SO-DI
  • Allure EC-Smart-Comfort-SF
  • Allure EC-Smart-Comfort-SF-DI
  • Allure EC-Smart-Comfort-SOF
  • Allure EC-Smart-Comfort-SOF-DI

These models offer different configurations and capabilities, with some featuring digital input cables for expanded functionality. The sensors connect to a controller's Subnet Port, forming a daisy-chained subnetwork bus that facilitates communication with other room devices. This architecture allows for a scalable and integrated control system.

Usage Features

The Allure EC-Smart-Comfort Series is tailored for occupants, emphasizing ease of use and immediate feedback. Key usage features include:

  • Intuitive Design: The device features a clean, modern aesthetic with clearly identifiable controls.
  • Coloured LED Indicators: These indicators provide visual feedback to the user, enhancing the interactive experience and confirming actions or status.
  • Rotary Knobs: Two primary rotary knobs are present:
    • Temperature Setpoint Offset Knob: Allows occupants to adjust their preferred temperature setpoint within a defined range, providing personalized comfort.
    • Fan Speed Selection Knob: Enables control over the fan speed, offering options like "Auto" and various manual settings (e.g., "Off," "1," "2," "3").
  • Occupancy Button: A dedicated push-button allows occupants to apply an occupancy override, signaling their presence and potentially activating or adjusting HVAC settings for comfort and energy efficiency.
  • Multi-Function Room Device: The sensor's design allows for expansion with up to four Smart-Light/Blind Series add-on push-button modules. These modules enable integrated control of lighting and shade/sunblind systems directly from the same wall-mounted unit, consolidating room control functions into a single, convenient interface.
  • Digital Input Capability: Certain models (e.g., -S-DI, -SO-DI, -SF-DI, -SOF-DI) include a digital input cable connector, allowing for the integration of external switches or sensors. This feature enhances the device's versatility, enabling control over additional room functions or the monitoring of external conditions. The digital inputs can be configured for various purposes, such as connecting 2-pole switches (e.g., ON-OFF light switches) or 3-point switches (e.g., UP/DOWN lighting or shade switches).
  • Subnet ID and EOL Termination: The device incorporates DIP switches for configuring the Subnet ID address and EOL (End-Of-Line) termination. These settings are crucial for proper communication within the subnetwork bus, ensuring that each sensor has a unique address and that the bus is correctly terminated to prevent signal reflections.

Maintenance Features

Maintaining the Allure EC-Smart-Comfort Series is straightforward, focusing on cleanliness and proper handling to ensure longevity and accurate performance.

  • Cleaning: The device can be gently cleaned using a soft, lint-free cloth slightly moistened with a solution of mild liquid dish soap and warm water. For disinfection, a soft cloth slightly moistened with 70% isopropyl alcohol is recommended. It is important to avoid directly spraying any liquid or disinfecting solution onto the device and to refrain from using other chemical products, as these could damage the unit.
  • Installation Precautions: To ensure proper operation and prevent damage, several installation guidelines are provided:
    • Temperature Acclimatization: Products should be kept at room temperature for at least 24 hours before installation to allow any condensation from temperature changes during shipping/storage to evaporate.
    • Inspection: Upon unpacking, the product should be inspected for shipping damages. Damaged modules should not be installed.
    • Environmental Conditions: The device is designed for specific environmental conditions as detailed in its datasheet. It should be installed in an area with proper ventilation, avoiding corrosive, deteriorating, or explosive vapors, fumes, or gases.
    • Physical Handling: The device should not be dropped or subjected to physical shock. When handling the sensor, care should be taken to avoid installing it on a vibrating surface, which could affect reading accuracy.
    • Wiring Connections: Connections to the product should be made last. Yanking the cable while it is attached can damage the connector.
    • Electrostatic Discharge (ESD) Prevention: Reasonable precautions should be taken to prevent electrostatic discharges during installation, servicing, or operation. Discharging any accumulated static electricity by touching a grounded object with a hand before handling the product is advised.
    • Location Selection: The device should not be installed on exterior walls, near heat sources, near air discharge grills, or in places where it can be affected by direct sunlight. It requires an area that provides proper device ventilation, ensuring nothing restrains air circulation. The sensor is not designed for outdoor use.
  • Warranty: Any modification to a Distech Controls product will void the product's warranty, emphasizing the importance of adhering to manufacturer guidelines.
  • Disposal: The device is marked with the WEEE symbol, indicating that it should not be disposed of as municipal waste. Products must be disposed of according to local regulations and the WEEE Directive at the end of their useful life.

The Allure EC-Smart-Comfort Series is a robust and user-friendly solution for modern building automation, combining advanced sensing capabilities with intuitive occupant controls and flexible expansion options.

Distech Controls Allure EC-Smart-Comfort Series Specifications

General IconGeneral
CategoryControl Systems
Power Supply24 VAC/VDC ±10%
Number of Analog Outputs2
Number of Digital Outputs2
DisplayLCD
Communication ProtocolBACnet MS/TP, Modbus RTU
Operating Temperature50 °C (32 to 122 °F)
Storage Temperature70 °C (-4 to 158 °F)