13
DischargeHumiditySensorAlarm_1
MSV 26
Sensor Alarm [MSV
Enumerated] Y
DischargeHumiditySensorAlarm_2
MSV 27
Sensor Alarm [MSV
Enumerated] Y
ReheatBurnerLockoutAlarm MSV 28
Alarm [MSV
Enumerated] (unit was
commanded on for 2
minutes and fan motor
did not start) Y
DirtyFinalFitlerAlarm MSV 4
Dirty Filter Alarm [MSV
Enumerated] Y
OutsideHumiditySensorAlarm 1 MSV 8
Alarm [MSV
Enumerated] Y
MotorNotRespondingAlarm 1 MSV 10
Alarm [MSV
Enumerated] (unit was
commanded on for 2
minutes and fan motor
did not start) Y
FanCommand BV 8
(enumerated 0=Off /
1=On) Y
UnitDesignCFM AV 10
when airflow
monitoring and control
not available) Y
ManualVFDSpeedPercent AV 11
Point (overrides
automatic VFD control /
use 'null' value for
automatic control) Y
UnitInstallationAltitude AV 12
Sea Level at which the
unit is installed Y