DischargeSensorCount BV 6
Number of Discharge
Temp/Humidity Sensors
Available Y
AirflowAvailable BV 7
Airflow (DFM)
Monitoring and Control
Available Y
DischargeeTempSetPoint AV 5
Discharge
Temperature
Set Point Y
DischargeHumiditySetPoint AV 6
Discharge Humidity Set
Point Y
DischargeAirflowSetPoint AV 7
Discharge Airflow (DM)
Set Point Y
PreHeatBurnerReset AV 8
Preheat Burner Reset
Command Y
ReheatBurnerReset AV 9
Reheat Burner
Reset
Command Y
OutsideTemperature AV 36 Outside Temperature Y
OutsideHumidity AV 37 Outside Air Humidity Y
CoilExitTemperature AV 38 Coil Exit Temperature Y
PreheatExitTemperature AV 39 PreheatExitTemperature
Y
DischargeTemperature AV 40
Discharge Air
Temperature Y
DischargeHumidity AV 41 Discharge Humidity Y
DischargeAirflowCFM AV 42 Discharge Airflow CFM Y
CoolingCommand AV 43
Cooling Command
Precent Y
PreheatCommand AV 44
Preheat Command
Percent Y
HumiditficationCommand AV 45
Humidification
Command Percent Y
ReheatCommand AV 46
Reheat Command
Percent Y
DirtyFinalFilterAlarm MSV 21
Dirty Filter Alarm [MSV
Enumerated] Y
CoilExitTempSensorAlarm MSV 22
Coil Exit Sensor Alarm
[MSV Enumerated] Y
PreheatTempSensorAlarm MSV 23
Preheat Sensor Alarm
[MSV Enumerated] Y
DischargeTempSensorAlarm_1 MSV 24
Discharge Temp Sensor
Alarm [MSV
Enumerated] Y
DischargeTempSensorAlarm_2 MSV 25
Discharge Temp Sensor
Alarm [MSV
Enumerated] Y