EasyManua.ls Logo

doble f2250 series - Table 4.6 Parameter Rate-Of-Change Per Second at 60 Hz

doble f2250 series
298 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F2250 User Manual
72A-1146 Rev. D 8/99 4-49
Table 4.6 and Table 4.7 show the range of VALUE/TIME ramps
based on parameter resolution.
Table 4.6 Parameter Rate-of-Change per second at 60 Hz
No. Cycles Amplitude & Phase Angle (L.S.D.) Resolution
0.001 0.01 0.1
1 0.06/second 0.6/second 6/second
2 0.03/second 0.3/second 3/second
3 0.02/second 0.2/second 2/second
4 0.015/second 0.15/second 1.5/second
5 0.012/second 0.12/second 1.2/second
6 0.01/second 0.1/second 1.0/second
7 0.008/second 0.085/second 0.857/second
8 0.007/second 0.075/second 0.75/second
9 0.0066/second 0.066/second 0.66/second
10 0.006/second 0.06/second 0.6/second
20 0.003/second 0.03/second 0.3/second
30 0.002/second 0.02/second 0.2/second
40 0.0015/second 0.015/second 0.15/second
50 0.00125/second 0.0125/second 0.125/second
60 0.001/second 0.01/second 0.01/second
70 0.0008/second 0.008/second 0.085/second
80 0.0007/second 0.0075/second 0.075/second
90 0.00066/second 0.0066/second 0.066/second
99 0.0006/second 0.006/second 0.06/second

Table of Contents