TDR9000
Circuit Breaker Test System
Users Guide
Doble Engineering Company
85 Walnut Street
Watertown, Massachusetts 02472-4037
(USA)
www.doble.com
PN 500-0314 72A-1898 Rev. A 11/01

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the doble TDR9000 and is the answer not in the manual?

Overview

The Doble TDR9000™ Circuit Breaker Test System is a multi-purpose data recorder designed to measure, analyze, and record the electrical and mechanical performance of circuit breakers in the field. Its modular design and user-friendly interface allow for a wide array of configuration possibilities, supporting both on-line and off-line Live Tank and Dead Tank circuit breaker tests. The system can also read inputs from various external data collection devices connected through its Event module channels.

Function Description:

The TDR9000 system, in conjunction with the TRXField™ software, offers flexible testing capabilities. It allows for the configuration of test command parameters and access to circuit breaker specifications for comparative purposes. This integrated approach simplifies the performance of multiple tests under varying conditions. After a test, results can be viewed in tabular and graphical formats, with the ability to overlay results from different tests for comparison. The system compares test results against circuit breaker specifications and provides a Pass or Fail determination for each measurement with a comparative value set in the Test Plan. Field data can be transferred to a computer running the TRX™ software for database storage, record keeping, and test interpretation.

The system supports a variety of circuit breaker and ancillary tests, including:

  • Trip (O)
  • Close (C)
  • Reclose (O-C)
  • Trip Free (C-O)
  • O-C-O
  • First Trip
  • First Close
  • Slow Close
  • Continuity
  • Capacitance
  • Self-Diagnostics

Important Technical Specifications:

The TDR9000 is comprised of several modules, each with specific characteristics:

OCB/Motion Module:

  • Function: Measures main contact timing of Dead Tank circuit breakers, pre-insertion resistor switch timing, and ohmic value of pre-insertion resistors (optional). It also measures linear or rotary movement using TR3190 or TR3160 motion transducers.
  • Main Contact Channels: 3 channels with 1 break per phase.
  • Contact Sense Voltage: 48/15/7.5 VDC (modified by pre-insertion resistor value).
  • Close and Open Timing Resolution: 100 microseconds.
  • Close and Open Timing Accuracy: ± 100 microseconds.
  • Minimum Contact Bounce Measurement: 60 microseconds.
  • Pre-Insertion Resistor Value Range: 10 - 400 Ohms or 300 - 7000 Ohms.
  • Resistor Value Measurement Accuracy: ± 10%.
  • Linear Transducer Range: 0.0 - 40.0".
  • Linear Transducer Resolution: 0.00125".
  • Linear Transducer Accuracy: ± 0.1% of measured value, ± 0.1" max error.
  • Linear Transducer Display Resolution: 0.002".
  • Linear Transducer Velocity: 50 ft/sec max.
  • Linear Transducer Acceleration: 1200g for 50 µsec max.
  • Rotary Transducer Range: 0 - 2880°.
  • Rotary Transducer Resolution: 0.09°.
  • Rotary Transducer Display Resolution: 0.1°.
  • Rotary Transducer Accuracy: ± 0.1% of measured value, ± 0.1° max error.
  • Rotary Transducer Velocity: 120 rev/sec max.
  • Rotary Transducer Acceleration: 30 x 10^6 deg/sec^2 max.

EHV Module:

  • Function: Measures main contact timing of Live Tank circuit breakers, pre-insertion resistor switch timing, capacitance of grading capacitors (optional), and ohmic value of pre-insertion resistors (optional).
  • Main Contact Channels: 6 channels with 2 breaks per phase.
  • Contact Sense Voltage: 15/7.5 VDC (modified by pre-insertion resistor value).
  • Close and Open Timing Resolution: 100 microseconds.
  • Close and Open Timing Accuracy: ± 100 microseconds.
  • Minimum Contact Bounce Measurement: 60 microseconds.
  • Pre-Insertion Resistor Value Range: 10 - 300 Ohms or 200 - 500 Ohms.
  • Resistor Value Measurement Accuracy: ± 10%.
  • Capacitance Measurement Range and Accuracy: 75 to 10,000 pF in the range of ± 5%.

Event Module:

  • Function: Monitors characteristics of the circuit breaker’s operating mechanism, used for First Trip/Close tests.
  • Analog Channels: 3 per module.
  • Analog Channel Sampling Frequency: 10 kHz.
  • Analog Channel Voltage Measurement Range: ± 300 DC/AC peak.
  • Analog Channel Signal Bandwidth: DC to 5 kHz.
  • Analog Channel Amplitude Accuracy: ± 0.5% of full scale, ± 0.5% of reading (± 0.5% of full scale, ± 1.5% of reading for the ± 300 V range).
  • Analog Channel Current Ranges: 0 - 20 A, 0 - 200 A (Probe).
  • Analog Channel Isolation Voltage to Ground: 300 V.
  • Auxiliary Contact Channels: 3.
  • Auxiliary Contact Sense: Open Wet/Open Dry/Close.
  • Auxiliary Contact Wetting Voltage: 28 VDC.
  • Auxiliary Contact Voltage Input: 0 - 300 VDC.

System Module:

  • Function: Provides basic system functionality (communications, power, test control) and interfaces for optional modules.
  • Trip/Close Module Peak Voltage: 300 VDC.
  • Trip/Close Module Maximum Current Non-Repetitive: 100 ADC (Trip pulse), 20 ADC (Close pulse).
  • Trip/Close Module Maximum Turn On/Off Time: 10 µsec.
  • Trigger In Voltage Input: 0 - 600 VDC.
  • Trip/Close Command Pulse Width: 8.0 to 1600 msec. / 0.5 to 96 cycles.
  • Trip/Close Command Resolution: 0.1 msec / 0.1 cycle.
  • Trip Command Current Range: 2/5/20/100 A.
  • Close Command Current Range: 0.2/1/5/20 A.
  • Delay Duration: 0 - 1600 msec/ 0 - 96 cycles.
  • Delay Resolution: 0.1 msec / 0.1 cycle.
  • Recording Length (Circuit Breaker): 1.6 seconds.

Physical Specifications:

  • Enclosure: High impact, molded, flame retardant ABS. Meets National Safe Transit Association testing specification No. 1A for immunity to severe shock and vibration.
  • Dimensions: 10.0" H x 16.0" W x 15.5" D (25.4cm x 40.6cm x 39.4cm).
  • Maximum Weight: 30 lbs. (13.6 kg) - includes cover, printer and maximum configuration.
  • Supply Voltage: 100 - 240 VAC 50/60 Hz.
  • Electrostatic Discharge Immunity: Meets IEC 1000-4-2 Level 4 (formerly IEC 801-2).
  • Surge Withstand Capability: Meets ANSI C37.90 1989 ESD.

Environmental Specifications:

  • Storage Temperature Range: –25° C to +70° C.
  • Operating Temperature Range: 0° C to +50° C.
  • Storage Humidity: 95%, non-condensing.

Usage Features:

  • Modular Design: The TDR9000's modularity allows for flexible configurations to suit various testing needs, including Live Tank and Dead Tank circuit breakers, and integration with external data collection devices.
  • TRXField™ Software: The accompanying software provides a virtual front panel for intuitive control and configuration of tests. It enables users to configure test values, select test types, run tests, view and interpret results, and save test plans and results.
  • Test Plan Management: Users can create, modify, and store Library Test Plans and Breaker Test Plans, simplifying repetitive testing and ensuring consistency.
  • Graphical and Tabular Results: Test results are presented in both graphical and tabular formats, with options for zooming, overlaying different tests for comparison, and re-ordering channels.
  • Smart Cursor: A specialized cursor in the virtual front panel aids in configuring modules by displaying relevant information and allowing access to module and connector level settings.
  • Triggering Options: Supports internal, AUX Contact, and Trigger In sources for initiating tests, providing flexibility for different testing scenarios. Trigger Output capabilities are also available for controlling external accessories or triggering other devices.
  • Current Probe Zeroing: Includes procedures for zeroing current probes to maximize measurement accuracy, with visual and auditory feedback.
  • Firmware Updates: The system supports field upgrades of its firmware, ensuring it remains up-to-date with the latest features and improvements.
  • Printer Option: An optional Pentax® PocketJet II™ thermal printer can be integrated for on-site printing of Test Plans, tabular results, and graphical results.

Maintenance Features:

  • Self-Diagnostics Test: Performs a two-tiered analysis of machine functionality, including a Global Self Test and a Local Self Test, to identify and localize failures to the circuit board/module level.
  • LED Indicators: Internal circuit board LEDs and an external LED on the System module provide visual cues for proper operation and troubleshooting.
  • Troubleshooting Flow Charts: Comprehensive flow charts guide users through diagnosing problems based on symptoms, from TDR9000 indications to circuit board level issues.
  • Problem/Solution Table: A table lists common problems and their associated solutions, including checks for mounting, line frequency, and cable connections.
  • Replaceable Parts: Procedures are provided for replacing internal circuit boards, physical front panel modules, power supply fuses, and the power supply module.
  • Cable Verification: A Continuity Test is recommended to verify the proper working condition of contact monitor cables.
  • Customer Service Support: Detailed instructions are provided for contacting Doble Customer Service, including information to have ready for efficient assistance.
  • Safe Packing Guidelines: Recommendations for packing the TDR9000 for shipment, including material specifications and the importance of obtaining a Repair Work Order (RWO) number.

doble TDR9000 Specifications

General IconGeneral
Branddoble
ModelTDR9000
CategoryTest Equipment
LanguageEnglish