Close Test Tabulation
A-110 72A-1898 Rev. A 11/01
Monday, November 26, 2001 1:09 pm
Figure A.130 Dead Tank Breaker Trip Tabular Report (Continued)
Close Test Tabulation
This discussion presents results for a Close test, with explanations of the
origination of important results. The Breaker Report is shown in
Figure A.131.
A The auxiliary switch monitored by the AUX contact
triggers the timing of the Main Contacts, which
happens to be 15.3 ms after test initiation
(Figure A.133 on page A-113). This is useful when
timing specifications are based on close coil
energization rather than test initiation.
Main Contact Opening Time Measured From Test Initiation
Specifications | Test results | Travel | Velocity | Compare
Maximum ****** mS | PHASE 0 24.0 mS | 4.299 cm.| 5.207 m/s|
Minimum ****** | PHASE 4 24.3 | 4.455 | 5.239 |
| PHASE 8 24.0 | 4.299 | 5.207 |
Delta Main Contact Opening Time Within the Breaker
Specifications | Test results | Compare
Maximum ****** mS | Breaker 0.3 mS |