Leakage Reactance Test Procedures
3-18 72A-2243-01 Rev. B 9/04
September 17, 2004
16. Repeat the test for each phase of the winding, making sure the correct
column is highlighted before starting.
17. Start a new Leakage Reactance form for each pair of windings being
tested. You will need three forms for a three-winding transformer, and six
for a four winding transformer.