Troubleshooting CRX
34
Compressor is not running (connected to AC supply)
Start attempt with
U
Term
≤ U
OFF
Loose cables
Poor contact (corrosion)
Establish a connection
Battery capacity too low Replacing the battery
Cable cross section too small Replace the cable
(fig. d, page 10)
Start attempt with
U
Term
≥ U
ON
Ambient temperature too high –
Insufficient ventilation Move the refrigerator to
another location
Condenser is dirty Clean the condenser
Electric circuit between
the pins in the compres-
sor interrupted
Defective compressor Contact customer service
U
Term
Voltage between the positive and negative terminals of the electronics
U
ON
Cut-in voltage of the electronics
U
OFF
Cut-off voltage of the electronics
Problem Possible cause Remedy
No voltage Connection supply line interrupted Establish a connection
Main switch faulty (if installed) Replace the main switch
Additional supply line fuse has blown
(if installed)
Replace the supply line
fuse
Voltage is present but
the compressor doesn't
run
Ambient temperature too high –
Insufficient ventilation Move the refrigerator to
another location
Condenser is dirty Clean the condenser
Electric circuit between
the pins in the compres-
sor interrupted
Defective compressor Contact customer service
Problem Possible cause Remedy