Service codes DSP-EM
6
4 Service codes
Service code Description Range
Stand
ard
value
Device
S-00 Setting of the
connected devices
only battery sensor MCA-HS1 1 3 Display
only MCA battery charger 2
Battery sensor MCA-HS1 and MCA bat-
tery charger
3
only DSP-T inverter 4
Battery sensor MCA-HS1 and
DSP-T inverter
5
MCA battery charger and DSP-T inverter 6
Battery sensor MCA-HS1, MCA battery
charger and DSP-T inverter
7
DSP-C inverter 8
Battery sensor MCA-HS1 and
DSP-C inverter
9
S-01 Output voltage Sets the output voltage of the inverter. 230 V or 240 V 230 V DSP-T, DSP-C
S-02 Output frequency Sets the frequency of the output voltage. 50 Hz or 60 Hz 50 Hz DSP-T, DSP-C
S-03 Standby mode Switches standby mode ON/OFF. ON, OFF ON DSP-T, DSP-C
S-04 Standby timer Sets the time in standby mode after
which the inverter switches off.
OFF, 5 min to 30 min
in 5 min intervals,
1h to 24h
in 1 h intervals
20 min DSP-T, DSP-C
S-05 Standby delay Sets the time after which the inverter
switches to standby mode if no load is
present.
10 s, 1 min to 10 min 10 s DSP-T, DSP-C
S-06 Standby threshold Sets the power at which the inverter is
activated from standby mode.
OFF, 1 W, 5 W to 45 W 1 W DSP-T, DSP-C
S-07 DC high-voltage
shutdown
Sets the upper voltage value at which
the inverter switches off.
15 V to 16.5 V
in 0.1 V intervals
16.5 V DSP-T, DSP-C
S-08 Upper DC restart
voltage
Sets the voltage at which the inverter
switches on again after a high-voltage
shutdown.
no recovery,
13 V to 16.4 V
in 0.1 V intervals
15.5 V DSP-T, DSP-C
S-09 DC low-voltage
shutdown
Sets the lower voltage value at which the
inverter switches off.
10 V to 11.5 V
in 0.1 V intervals
10.5 V DSP-T, DSP-C
S-10 lower DC restart
voltage
Sets the voltage at which the inverter
switches on again after a low-voltage
shutdown.
no recovery,
10.1 V to 14.5 V
in 0.1 V intervals
12.5 V DSP-T, DSP-C
S-11 Advance warning
setting
Sets the value from which an imminent
switch off is displayed.
OFF,
0.1 V to 2.0 V
in 0.1 V intervals
0.5 V DSP-T, DSP-C
S-12 Battery type Sets the battery type. 0: Lead acid
1: Gel
2: AGM
3: eStore
4: Custom
0IBS and IBS
multiplexer
S-13 Battery capacity Sets the capacity of each battery sensor. 10 Ah to 249 Ah 100 Ah IBS and IBS
multiplexer
S-14 Battery charging
current
Sets the maximum battery charging
current, as a percentage of the rated
charging current.
25 %, 50 %, 75 %,
100 %
50 % DSP-C
DSP-EM-Service-16s.book Seite 6 Dienstag, 29. Januar 2019 3:08 15