BOOSTER PUMP SYSTEM 13
BOOSTER PUMP SYSTEM N747D
6. After setting, press save” .
The adjustable items in the user setting [1] are as below.
- Setting pressure: Target water pressure to operate.
Change of predetermined pressure.
(Example: In case current set value is 03.00 kgf/cm² )
1. Using
Key, select .
2. Initially the first ‘0’ of the ’03.00’ blinks.
3. Using
Key, select position to be changed in ‘03.00 kgf/cm² ‘.
4. After change using
Key, make sure to press Key.
Set value is not changed until input key is pressed.
When predetermined pressure is changed, the high pressure value becomes
setting pressure +2kgf/cm² automatically.
………………………………………………………………………………………………………-
-The change of auxiliary stop pressure
(Example: In case current set value is 00.2 kgf/cm²)
1. Using
Key, select
2. Initially the first ‘0’ of the ’00.20’ blinks.
3. Using
Key, select position to be changed in ‘00.20 kgf/cm².
4. After change using
Key, make sure to press Key
- Auxiliary stop pressure : it means the pressure to stop the auxiliary pump.
When current pressure decreases hoigher than “setting pressure + auxiliary operation
pressure”, then auxiliary pump will stop. If setting pressure is 03.00 kgf/cm² and auxiliary
pressure is 00.50kgf/cm², 005 second, and current pressure is higher than 3.5kgf/cm²,
then auxiliary pump will stop after 5 seconds.
Change of auxiliary stop pressure.
(Example: In case current set value is 00.30 kgf/cm² )
1. Using
Key select .
2. Initially the first ‘0’ of the ’03.00’ blinks.
3. Using
Key, select the position to be changed in ’00.30 kgf/cm²’.
4. Using
Key, change to required value, then make sure to press Key.
Set value is not changed until input key is pressed.