BOOSTER PUMP SYSTEM 55
BOOSTER PUMP SYSTEM N747D
2. Check items
1. No operation is started when powered ON;
Check power voltage (208V~440V).
Check power, wire short and contact terminals.
2. When powered ON, only LCD Back Light is turned on;
Turn VR counterclockwise with PIN driver.
Check cables connected to LCD.
3. No front Key works;
Check cables connected to control board Key.
4. After set front panel switches for pump #1, Pump #2 and Pump #3
at AUTO position, no pump is not identified on the LCD screen;
Check switch contact points.
Verify the shortages of 5. PENT and 12. CG wire of Pump-OPT
board.
Check the contact point of 5. PENT and 12. CG wire of Pump-
OPT board.
(Verify LED ON state of Pump-OPT board.)
5. “Start/Stop” switch of the front panel does not work;
Check switch contact points.
Verify the shortages of 20.CG and 25. Run wire of main board.
Verify the contact points of 20.CG of main board and 25. Run
wire. (Verify LED ON state of main board.)
6. The output of inverter is not sufficient;
(EX. While front LCD shows 100%, internal inverter operates in
50Hz.)
Adjust DAC value in installer’s settings.
7. While the inverter is displayed on front LCD, pump does not work;
Check wire shortage and contact points of 18.RI0C and
19.RI0A of main board.
Verify if any short raises in 18. RI0C and 19. RI0A wire. ( RUN
signal work when short)
Verify the shortages and contact points of 35.VO0 and
36.CGwire.
Check DC voltage of 35. VO0 and 36. CG wire in main board.
(EX. DC 5V = 30Hz, DC10V = 60Hz)