56 BOOSTER PUMP SYSTEM
BOOSTER PUMP SYSTEM N747D
8. MC does not work in each pump;.
Check if each MC power is 220 V.
Verify shortages and contact points of 1. IPA, 2. IPC, 3. DPA
and 4. DPC wire in Pump-OPT.
9. There is big gap between analog pressure gauge and the current
pressure of LCD screen;
Check the maximum pressure sensor value in use.
Adjust the maximum pressure sensor value in the installer’s
setting screen.
10. Analog pressure gauge is very close to the current pressure of
LCD screen;
Adjust sensor correction value in the installer’s setting screen.
11. Main pump and auxiliary pump operate continuously;
Check the rotation direction of the pump ( it’s possible in test
operating).
Re-set the operating pressure and time of the auxiliary pump.
12. Auxiliary pump operates frequently;
In the user setting screen, re-set the operating pressure and
time of auxiliary, sequential stop pressure and time.
13. Only main pump operates.
In the user setting screen, re-set the shift time of main pump.
Shift the pump by operator with the front switch.
14. Frequent starting phenomenon happens in emergent operation
due to the inverter trouble;
In the user setting screen, re-set the sequential operation
pressure and time, sequential stop pressure and time.
15. It is changed to “sequential operation 2” by user;
Adjust the deviation of pressure switch.
16. Various alarms raise (Buzzer, Lamp operates);
Enter front numeric Key and initial screen Key once. (Buzzer
OFF, Lamp OFF)
Check the caused troubles and take corrections.