[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-7 |
DOOCHPUMP
Pr-03 Sensor 1 Capacity Setup
Enter the maximum value that the pressure sensor can measure.
By entering capacity of pressure sensor attached to the drive being used, it is possible to display
the currently measured pressure.
Example) In case the using sensor has 10bar, enter 10.0.
If the using sensor has 16bar, enter 16.0.
and enter the rated value of the pressure sensor for normal pump operation.
Factory Setting Input Range
]rab[ 0.52 ~ 0.0 ]rab[ 0.61
Pr-04 Sensor 1 Correction Setup
It corrects pressure variation between analog or digital pressure meter and the one displayed on
drive FIND.
Factory Setting Input Range
]rab[ 0.1 ~ 0.1- ]rab[ 0.0
Pr-05 Sensor 2 Capacity Setup
It is used in case of pressure difference control mode.
Setup method is same as described on Pr-03.
Pr-06 Sensor 2 Correction Setup
It is used in case of pressure difference control mode.
Setup method is same as described on Pr-04.
Pr-07 P Gain of PID Controller
It is relevant to ‘P’ (Proportional Constant) out of PID control parameters.
If Reference and Feedback is in pressure unit [bar], PID P-Gain 100% means that if PID I-Gain is
0 and 100bar error is maintained, controller output is 1.0[Hz].
Factory Setting Input Range
]%[ 001 ~ 0 ]%[01