EasyManua.ls Logo

dooch Q-Drive NQ-0150-T - Pump Control Parameters

Default Icon
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-2 |
DOOCHPUMP
6.2 Pump Control Group
DISPLAY Name Range
Factory
Setting
Para.
Link
Diff.
Pressure
Use
Change
on
Operation
Ref.
Page
Pr-00 Jump Code 1~92
51 X O O
Pr-01 Pump Capacity Setup 0.75~25.00[kW] - X O X
Pr-02 Pump Control Mode 0~1 1 O O X
6-6
Pr-03
Capacity Setup of
Sensor1
1.0~25.0[bar] 16.0 X Ο X
Pr-04
Correction Value of
Sensor1
-1.0~1.0[bar] 0.0 X Ο O
Pr-05
Capacity Setup of
Sensor2
1.0~25.0[bar] 16.0 Χ Ο X
Pr-06
Correction Value of
Sensor2
-1.0~1.0[bar] 0.0 Χ Ο O
Pr-07
P Gain of PID
Controller
0~100[%] 10 Ο Ο O
6-7
Pr-08
I Gain of PID
Controller
0~100[sec] 1 Ο Ο O
Pr-09
D Gain of PID
Controller
0~100[ms] 0 Ο Ο O
Pr-10
Control Cycle of PID
Controller
10~200[ms] 200 Ο Ο X
Pr-11
Selection of Freezing
Prevention
0~1 0 Ο Ο O
6-8
Pr-12
Starting pressure
Variation
0~2.0[bar] 0.3 Ο Χ O
Pr-13
Stopping Time after
reaching Setup
Pressure
5~200[sec] 30 Ο Χ O
Pr-14
Ratio of Min Output
Freq. of Stop Mode
after reaching Setup
Pressure
0~100[%] 100 Ο Χ O
Pr-15
Ratio of Initial Output
on Starting
5~100[%] 50
0~1
1~250
1~5
1~9999[ms]
0
1
4
5
Ο
Ο
Ο X
ΟΟ X
ΟΟ X
ΟΟ X
X
X X
6-9
Pr-40 485 Comm. Mode
Pr-41 485 Comm. ID
Pr-42 485 Comm. Speed
Pr-43 Comm. Delay time
Pr-50
CAM Comm.
Mode
0~1 1 X Ο
6-10
6-11
Pr-51 CAN Comm. ID 0~6 0 X Ο X

Table of Contents