[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-4 |
DOOCHPUMP
6.3 Drive Control Group
To setup initial value according to drive capacity
To setup initial value with basis of Dooch induction motor
DISPLAY Name Range Factory Setting
Change
on
Operation
Ref.
Page
dr-01
dr-00
Command Input Location
CAN Comm. Speed 1~90 1
Setup
0~1 0 X
dr-02
Target Freq. Input
Method Setup
0~3 0 X
dr-03 Target Freq. Value Setup
Min Freq. (dr-42)~Max
Freq.
30.0 O
O
6-15
dr-10 Motor Capacity Selection 0.10~75.00[kW]
X
dr-11
No. of Motor Poles
Selection
1~2 1 X
dr-12 Rated Current of Motor 1.0~100.0[Arms]
X
dr-13 Rated Rotations of Motor 1~9999[rpm]
X
dr-14 Rated Voltage of Motor 200.0~500.0[Vrms]
X
6-16
dr-15
Non-load Current of Motor
0.5~100.0[Arms]
X
dr-16
Rated Slip Frequency of
Motor
0.10~10.00[Hz]
X
dr-17
Rated Frequency of
Motor
0~1 1 X
dr-18 Efficiency of Motor 50~100[%]
X
6-17
dr-20
Rotation Direction
Selection of Motor
0~1 0 X
dr-21
Stopping Method of
Motor
0~1 0 X
dr-22 Increase Time 1.0~600.0 3.0 O
dr-23 Decrease Time 1.0~600.0 6.0 O
6-18
dr-30
Motor Overload Trip
Selection
0~1 0 O
dr-31
Motor Overload Trip
Level
100~200[%] 120 O
dr-32
Motor Overload Trip
Time
5~200[sec] 60 O
dr-33 Stoll Prevention Setup 0~1 0 X
dr-34 Stoll Prevention Level 100~200[%] 150 X
dr-35
Motor Overheat
Selection
0~1 0 O
dr-36 Ground Detection 0~1 0 O
dr-37 No. of Restart after Trip 0~50 3 O
6-20
6-19

Table of Contents

Related product manuals