[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-17 |
DOOCHPUMP
dr-15 Non-load Current of Motor
ㆍ It sets non-load current of motor.
Factory Setting Input Range
Initial value is set upon drive capacity 0.5 ~ 100.0 [Arms]
dr-16 Rated Slip Freq. of Motor
ㆍ It displays slip freq. of motor.
Settings are automatically set upon No. of motor poles, rated No. of rotations, and rated
frequency.
Factory
Setting
Input Range
Related Function
dr-11 No. of motor poles
dr-13 Rated No. of Rotations of Motor
Automatic
Setup
0.10~10.00[Hz]
dr-17 Rated Frequency of Motor
dr-17 Rated Frequency of Motor
ㆍ It sets rated frequency of motor.
Setup Data Functional Description Related Function
50[Hz] 0
1 (Factory Setting) 60[Hz]
dr-43
Max Operation
Freq.
dr-18 Efficiency of Motor
ㆍ It is set when pump drive is released from the factory.
Factory Setting Input Range
Initial value is set upon drive capacity 70 ~ 100 [%]
※ Motor related constants (dr-10~dr-18) set upon drive capacity may not match with motor data of
the user. Be sure to check data on the nameplate.
dr-13 No. of Rated Rotations of Motor
ㆍ It sets No. of rated rotations of motor. It is based on data indicated on the nameplate of the motor.
Factory Setting Input Range
Initial value is set upon drive capacity 1 ~ 9999 [rpm]
dr-14 Rated Voltage of Motor
ㆍ It sets rated voltage of motor. It is based on data indicated on the nameplate of the motor.
Factory Setting Input Range
Initial value is set upon drive capacity 200.0 ~ 500.0 [Vrms]