Rack Monitor 88XX
Document: Operation Manual
Date: January 2024
Version: A.0 subject to change
Page 13 of 43 – Operations Manual
The AUX1 relay can be utilized for additional functions. Please contact OPW for possibilities
3. A user selectable (normally open - common - normally closed) AUX2 relay is available for four predefined
functions. See table at Error! Reference source not found. for dipswitch settings.
Front Layout
GROUNDING INDICATORS
COMPARTMENT STATUS INDICATORS
BYPASS INDICATORS
COMMUNICATION INDICATORS
GROUNDING ERROR INDICATOR
SilSil
Figure 1 (Shown with cable glands. 88XX models use rigid conduit)
Above are the two models Rack Monitor, a 88X0 and a 88X1. The 88X1 has two multicolor light bars. The top light
bar is usually used to indicate if a proper ground connection of the tank truck has been established. The bottom bar
is mainly used to indicate the status of the sensors.
Indication pattern depends on dipswitch setting 1-6. If this switch is on (up position) than the light pattern is
according the 8130 rack monitor. In .
the monitor indicators of a 8130 are shown. Note a 8130 is a simple 5-wire
rack monitor.
Red indicator ON means NON-PERMISSIVE; while a Green indicator ON means Permissive. Both Red and Green
will be on when the bypass is activated. The Red lamp will flash if there is no GROUND VERIFY sign.