Rack Monitor 88XX
Document: Operation Manual
Date: January 2024
Version: A.0 subject to change
Page 36 of 43 Operations Manual
State
Value
Description
Initial/Unknown
0
Initial value, probe status can’t be determined
Non permissive
1
No permissive signal from probe
permissive
2
Probe is permissive
Non permissive latched
3
Probe was non-permissive, but is now permissive
Out of spec
4
Probe doesn’t follow specification
Open
5
Probe channel open (2-wire only)
Short to ground
6
Probe channel shorted (2-wire only)
Short to other channel
7
Probe channel shorted to different channel (2-wire only)
Bypassed non-permissive
8
Probe is bypassed and currently non-permissive
Bypassed permissive
9
Probe is bypassed and currently permissive
Table 10 Probe states
Rack Status
The rack status register has several status flags. Flag 0 is bit 0 of the register.
Flag
Meaning
Flag 0
5-wire detected
Flag 1
2-wire detected
Flag 2
Sensors are permissive
Flag 3
Ground loop detected
Flag 4
Ground bolt detected
Flag 5
Ground verified
Flag 6
Rack permissive
Flag 7
Red function key detected
Flag 8
Blue function key detected
Flag 9
Rack is in bypass
Flag 10
Probes are bypassed
Flag 11
Ground verification is bypassed
Flag 12
Ground restored status is active
Flag 13
Over-temperature detected inside housing
Flag 14
High humidity detected inside housing
Flag 15
Reserved
Table 11 Rack status
Channel Status
The status of channels 1..8 is given in the channel status registers.
Register 80
Register 81
Register 82
Register 83
MSB
LSB
MSB
LSB
MSB
LSB
MSB
LSB
Channel
1
Status
Channel
2
Status
Channel
3
Status
Channel
4
Status
Channel
5
Status
Channel
6
Status
Channel
7
Status
Channel
8
Status
Table 12 Channel status registers