d. Select a button for Standard or ACR Mode (to turn on the ACR function).
e. Serial Number: 924B and DMP 1-Wire probes that are connected through the ISB (LX
Plus models only) are automatically recognized once they have been detected.
l If the console is an LX Plus model, the probes that were connected to the ISB and
detected in the System Settings/Info menu will show here.
l If the console is an LX4 model, the probe serial number must be entered manually.
NOTE: When a serial number is entered manually, a “QUERY” button will
come into view. When the “QUERY” button is selected, the console will try to
communicate with the probe to get information on the probe type (e.g 924B,
DMP-IS 1-Wire, DMP-IS RS485, XMT-SI-485 etc) and the number of floats
that are detected on the probe.
f. Probe type: If the console can successfully communicate with the probe to get its
configuration, this field will populate automatically.
l DMP-485: DMP-IS probe connected through RS485.
NOTE: With this selection the console thinks that the probe has 5 temperature
sensors and the applicable tank leak detection settings are automatically
detected.
DMP 1-WIRE: DMP-IS probe with 1-wire protocol connected on the ISB.
NOTE: With this selection the console thinks that the probe has 5 temperature
sensors and the applicable tank leak detection settings are automatically
detected.
l DMP FLEX: DMP flexible probe connected via RS485.
l DMP FLEX 1-wire: DMP flexible probe with 1-wire protocol connected on the ISB.
l XMT-SI-485: XMT-SI-485 probe connected through RS485.
l XMT-SI-RF: XMT-SI wireless probe connected through an RS485 RF Receiver.
l XMT-EXd: XMT explosion proof probe connected through RS485.
l OPW 924B: OPW 924B with 5 temperature sensors.
l OPW 924A: Previous generation OPW 924A probe with 5 temperature sensors.
l VSmart analog: For OPW 7100V flexible probes that connect through the Vsmart
module.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 34