Appendix - Maglink LX PLUS Pressurized Line
Leak Detection (PLLD)
Line Leak Setup
The Line Leak Setup menu is used to:
l Configure the PLLD-DAS (or older model I/O module) and the LIM (Line Interface Module).
l Configure the pipeline characteristics (length, size, Beta factor).
l Schedule leak tests (run a test now/later, run automatic testing).
1. Click on the “+” icon in the top menu bar to add a new PLLD configuration. Each PLLD sensor must
have its own configuration.
A. Settings
2. Number: Enter a number to identify the PLLD sensor configuration.
3. Enabled: When the “Enabled” button is in its ON position, the PLLD configuration is active. The system
will try to start tests on the applicable pipeline.
NOTE: If the “Enabled” button is OFF, then the system will not try to run tests on the
applicable pipeline. Pressure readings will not be received and the pipe stiffness calibration
procedure will not be able to start.
4. Name: Enter a name to identify the line.
5. Tank: Select the tank number from the drop-down that has the STP with the PLLD sensor installed.
MAGLINK I/O (PLLD-DAS in new software versions)