6. Sensor span: The default value is 87 psi. Do not change this value.
7. Address: Select address 1 for the first PLLD-DAS module, address 2 for the second PLLD-DAS
module, and so on.
NOTE: There can be more than one PLLD-DAS module connected to the LX Plus console.
Each PLLD-DAS module must have its address set by the dip switches on its motherboard.
Only one Maglink I/O module can be connected to the LX Plus console.
For more information on how to set the PLLD-DAS address Dip Switches, refer to the ID
Addresses/Dip Switches sub-section of the PLLD-DAS section of the M2050-PLUS MagLink
LX Plus Installation Manual.
8. Position: Enter the Position (connector slot) where the PLLD sensor is connected to the PLLD board.
n The PLLD board has 8 connector slots.
NOTE: For PLLD-DAS: Position 1 is at the top (CH1). See the illustration below.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 84