NO ANNUAL LEAK TEST (no annual leak test has been done as the WARNINGS setup in the Leak Test
tab)
PRESSURE LOW (the STP dispensing pressure is less than the Minimum Dispensing Pressure configured
at the Pipeline tab)
STP Shutdown
In the STP Shutdown tab the user can configure the conditions under which the STP will automatically
shutdown.
1. A 3 gph (11.36 lph) line leak fail will always shut down the STP.
2. Where applicable,select the STP to be shutdown during a 0.2 gph (0.76 lph) fail and/or a 0.1 gph (0.38
lph) fail.
3. The STP can also be configured to shutdown by other causes, (for example, high water detected by
the probe in the tank or by an environmental sensor activating).
a. To configure an event that will cause an STP shutdown, select ADD STP SHUTDOWN
REASON.
b. Select the applicable event.
c. The Delay is a timer that starts a countdown from the point in time the event was caused. The
STP will shutdown once the timer ends.
In the example shown in the image above, an HH Water alarm event on Tank 1 has been caused that will
shutdown the STP after 10 continuous hours that the alarm is active.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 90