Do you have a question about the D+H WRZ and is the answer not in the manual?
| Brand | D+H |
|---|---|
| Model | WRZ |
| Category | Accessories |
| Language | English |
Controls 230VAC ventilation drives based on environmental conditions.
Features LED displays for wind/rain and a signal memory function to prevent rapid cycling.
Allows adjustable wind force thresholds and signal retention times for WRZ and WRZ 8000 units.
Supports connecting up to 20 groups via TRL 8 relays and weather monitoring integration.
Separate weak current and supply mains wiring; observe clamp sequence and VDE 0100 regulations.
Connect max. 20 drives (30 VA each) or max. 20 cut-off relays TRL 8 to the 24 VDC output.
Use only buttons for deadman's principle operations with vent buttons.
Automatic mode functions when the green LED is lit (switch set to 'I').
System closes automatically when wind speeds exceed the set threshold; red 'Wind' LED indicates.
System closes automatically upon onset of rain; red 'Rain' LED indicates for at least one minute.
Room temperature control operates if automatic is on and no wind/rain signal is present; these signals have priority.
Details mains supply (230 VAC), power consumption (30 VA), and output ratings (230V/5A, 24VDC/0.5A).
Includes housing material (PC/light grey), protective system (IP 50), temperature range (-5°C to +40°C), and dimensions.
Illustrates the connection of WRZ/WRZ 8000 with 230V drive, RTR 230, WRG 82, and TRL 8.
Provides guidance for no function with rain/wind and faulty rain/wind indication.
Shows a typical setup with ventilation drive, room temperature control, wind/rain transmitter, and cutoff relay modules.
Contact details and copyright for D+H Mechatronic AG.