36
5.2.2 Function Parameter Reference (effective in program mode)
Table 5.2b Check frequency reference upper limit (Fn6) & lower limit (Fn7)
Key Operation Description
Digital Operator
Display
1
PRGM
(Fn)
*Enter program mode
*Display the current function code
FnXX
2 or keys
*Select the Fn6 by pressing up or down
keys to select the desired function code.
Fn 6
3
READ
ENTER
*Display the paramter of Fn6
*DATA lamp light
60.0
4 Repeat steps 1-3
*Display the parameter of Fn7
*DATA lamp lights
0.0
5 STOP
*Function parameter reference procedure
ends.
*Enter stopping mode
*Digital operator displays the current
frequency.
XXXX
DATA
DATA
* If function parameters can't be changed and "LOC" is displayed, this means function parameter is
locked. Please set Fn60 to 0 to release function parameter lock.
∧ ∨
Hz
5.3 Function code description
Fn0: Communication ID number (Range 0-32)
Fn0 identify the number of each inverter for RS232 and RS485 communication. Please refer to
communication operator manual for single mode operations. Set this to 1 when using the KN232
link communication package.
Fn1: Primary acceleration time (range 0.1 - 800.0 sec.)
Fn2: Primary deceleration time (range 0.1 - 30 sec.)
Fig. 5.3a Acceleration time
Fig. 5.3b Deceleration time