19
[29] Number of Rings Before Answering
Page 13
Default
1 2 Enter a number from 01 to 12 to set the number of rings before the panel will answer.
[30] Reset To Factory Default
Page 13
[31] 4th System Option Code
Page 14
Default Zone Light ON Zone Light OFF
OFF Zone Light 1 Enable download answer Disable answer
OFF Zone Light 2 Enable download callback Disable callback
OFF Zone Light 3 Answering machine over-ride Disable over-ride
OFF Zone Light 4 Show bypass status/armed
11
11
1
Show bypass status/disarmed
OFF Zone Light 5 AC = 50 Hz AC = 60 Hz
OFF Zone Light 6 Restore on bell time out Restore as follower
If zone light 4 is ON, bypass status will always be shown. If zone light 4 is OFF, bypass status is shown only when the panel is disarmed.
[32] 5th System Option Code
Page 14
Default Zone Light ON Zone Light OFF
OFF Zone Light 1 AC excluded from trouble AC included
OFF Zone Light 2 No bell during auto-arm Bell during auto-arm
ON Zone Light 3 Home/away with delay Home/away as interior
OFF Zone Light 4 Quick exit enabled Quick exit disabled
OFF Zone Light 5 Force arm on auxiliary delay Auxiliary delay normal
ON Zone Light 6 Standard Fire Temporal Fire
[33] Answering Machine Double Call Timer
Page 14
Default
0 6 0 Valid entries are 001 to 249
[34] 6th System Option Code
Page 14
Default Zone Light ON Zone Light OFF
OFF Zone Light 1 Audible Exit Delay with Urgency Standard Exit Delay
OFF Zone Light 2 Bell Squawk during Exit Delay No Bell Squawk during Exit Delay
OFF Zone Light 3 Audible Exit Fault enabled Audible Exit Fault disabled
OFF Zone Light 4 Urgency applied to Entry Delay Standard Entry Delay
OFF Zone Light 5 Bell Squawk during Entry Delay No Bell Squawk during Entry Delay
OFF Zone Light 6 [F] Key disabled [F] Key enabled
[35] LINKS1000 Test Reporting Code
Page 14
Default
NOTE: The LINKS1000 is not UL listed.
FF
Program this section only if the LINKS1000 Cellular Alarm Transmitter is being used with the PC1550.
[36] Keypad Lockout Control
Page 14
Default
Enter 2 2-digit numbers in the range of 00 to 99. Program the Number of Invalid Codes as 00 to disable the lockout feature.
0 0 Number of Invalid Codes before lockout
0 0 Lockout Duration (minutes)
[90] Installer’s Lockout Enable
Page 14
[91] Installer’s Lockout Disable
Page 14
WARNING!
Panels returned to DSC with the Installers Lockout enabled and no other apparent problems will be subject to an
additional service charge!
PC1550 Version 4.1