EasyManua.ls Logo

Dwyer Instruments CLS2 Series - User Manual

Dwyer Instruments CLS2 Series
5 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
351
Level Switches,
Capacitive
LEVEL
CAPACITIVE LEVEL SWITCH
Powder, Bulk, or Liquids, Auto-Calibration
The SERIES CLS2 Capacitive Level Switches is a capacitive technology level switch
which can be used for liquids, powders and bulk materials. It is offered with PVDF
and 316 SS wetted material, weatherproof enclosure, DPDT output and a variety of
process connections.
FEATURES/BENEFITS
No moving parts permitting for no jams, no wear, nothing to break, and no
maintenance
Impulse RF admittance measurement combined with an active guard, provides
excellent level measurement and stability while being insensitive to material buildup
Immune to external RF sources like walkie-talkies and cell phones as well as minimal
interference with radio communication or other electronic systems
Automatic calibration with no need to turn calibration pots, just push the calibration
button and an external magnet to activate the calibration without having to open the
enclosure saving time
Coat guard probe is not affected by sticky, dusty, or clingy materials that coat or build
preventing false alarms
Status indication via an ultra-high brightness external red LED switch status indicator,
and internal indicators for power, sensor, and switch status that can be seen
externally with window cap option (external LED on weatherproof model only)
Can be used for liquid interface applications to detect the level of two immiscible
liquids that have different dielectric constants such as oil and water
Failsafe setting with output switches that can be set for NO or NC condition on loss
of power
Time delay prevents false alarms from material splashing, agitation, etc.
Removable terminal block snaps in and out enabling easy wiring outside of the
enclosure
Universal power supply with one model that works from 12 to 240 VAC/DC without
any jumpers or change of setting
Wetted materials of PVDF and 316 SS assure great chemical compatibility and meet
food grade requirements
APPLICATIONS
Sewage and wastewater • Boilers and steam generators
Food and beverage • Caustics and acids
Pharmaceuticals • Reservoirs
Sumps • Level indication in silos
Level monitoring in receivers • Transporters in pneumatic conveying systems
4-3/16
[106.36]
Ø3/8
[Ø9.53]
4-5/32
[105.57]
3-19/32
[91.28]
4-1/8
[104.78]
2-19/64
[58.34]
22-21/64
[567.14]
19
[482.60]
SPECIFICATIONS
Service: Liquids, powder, and bulk materials compatible with wetted materials.
Wetted Materials: 316 SS and polyvinylidene uoride (PVDF).
Temperature Limits: Ambient: -40 to 185°F (-40 to 85°C), -4 to 185°F (-20 to 85°C)
with under 24 VAC/DC power supply; Process: -40 to 250°F (-40 to 121°C).
Pressure Limit: 365 psi (25 bar).
Enclosure Rating: Weatherproof, NEMA 4X (IP66).
Switch Type: DPDT (two form C).
Electrical Rating: 8 A @ 120/240 VAC res., 30 VDC. 1/2 hp @ 120 VAC and 1/4 hp
@ 240 VAC ind.
Power Requirements: 12 to 240 VAC/DC.
Power Consumption: 2.8 watts max.
Electrical Connection: 1/2˝ NPT conduit opening, screw termination with
removable terminal block.
Process Connection: See model chart.
Mounting Orientation: Vertical or horizontal.
Set Point Adjustment: Trips when product touches probe. Cut or extend probe
to length of desired trip point. Can be cut as short as 1˝ and can be extended by
welding on to probe. (Minimum length will be effected by material being sensed.)
Response Time: 0.2 s.
Time Delay: Adjustable, 0 to 60 s.
Spark/Static Protection: 10 M Ω dissipation resistance with spark gap. Surge
current to 100A max.
Sensitivity: 8 selectable settings, 1, 2, 4, 6, 8, 10, 14, 20 pF (at 30 pF nominal free
capacitance).
Agency Approvals: CE, cULus.
SERIES CLS2 | PROXIMITY
®
BY DWYER
®
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
V
I
D
E
O
O
N
L
I
N
E
MODEL CHART
Example CLS2 -W 1 1 R K 1 -019 -M20 CLS2-W11RK1-019-M20
Series CLS2 Capacitive level switch
Enclosure W Weatherproof
Switch 1 DPDT rated 8 A @ 12/240 VAC, 30 VDC res.
Power Supply 1 12-240 VAC/DC
Probe Type R
T
C
Standard rod: 316 SS, .375˝ diameter
Threaded rod: 316 SS (can attach 47˝ (1.2 m) eld extensions.*)
Cable: 316 SS with weight
Insulator Material K PVDF
Process
Connection
1
2
3
4
5
6
8
9
3/4˝ male NPT
1˝ male NPT
1-1/2˝ male NPT
3/4˝ BSPT
1˝ BSPT
1-1/2˝ BSPT
1-1/2˝ sanitary clamp
2˝ sanitary clamp
Probe Length XXX Insertion length in inches. Example 019 is 19˝ length. (Minimum length is 6˝, with 3/4˝ sensing tip)
Options M20
WC
M20 conduit connection with cable gland
Window cap
Example: CLS2-W11RK1-019.
*Extension rods sold separately.
Question and Answer IconNeed help?

Do you have a question about the Dwyer Instruments CLS2 Series and is the answer not in the manual?

Dwyer Instruments CLS2 Series Specifications

General IconGeneral
BrandDwyer Instruments
ModelCLS2 Series
CategorySwitch
LanguageEnglish

Related product manuals