Multi-State Value - Relay 2 Action
This object represents the relay 2 action setting. The selected action determines what
happens when the relay is active. If the selected source is an alarm, then the state text
values are “Close” and “Open”.
Binary Value - Enable External Input
This object represents the enable state of the external input. When enabled, the
external input is monitored and can be used to active a relay.
Multi-State Value - External Input Type
This object represents the type of contact/switch connected to the external input.
Positive Integer Value - External Input Activation Delay
This object represents the amount of time the external input must be continuously
active before it is considered active.
Binary Value - External Input Status
This object represents the current status of the external input. When active, the EXT
LED on the instrument face is illuminated.
Positive Integer Value - Damping Time
This object represents the time, in seconds, for the process measurement to reach
99.8% of the current input value. A value of 0 disables the damping feature.
Property Default Value Property Data Type Access
Object Identier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Number of States
State Text
MSV6
“Relay 2 Action”
Multi-State Value
1
{0,0,0,0}
Normal
No Fault Detected
FALSE
2
{“Direct”, “Reverse”}
BACnet Object Identier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Unsigned
BACnet Array[N] of
Character String
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Property Default Value Property Data Type Access
Object Identier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
BV11
“Enable External Input”
Binary Value
Active
{0,0,0,0}
Normal
No Fault Detected
FALSE
BACnet Object Identier
Character String
BACnet Object Type
BACnet Binary PV
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Property Default Value Property Data Type Access
Object Identier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Units
Max Pres Value
Min Pres Value
PIV2
“External Input
Activation Delay”
Positive Integer Value
0
{0,0,0,0}
Normal
No Fault Detected
FALSE
Mode Specic
3600
0
BACnet Object Identier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
BACnet Engineering
Units
Real
Real
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Read
Property Default Value Property Data Type Access
Object Identier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Number of States
State Text
MSV7
“External Input Type”
Multi-State Value
1
{0,0,0,0}
Normal
No Fault Detected
FALSE
2
{“Normally Open”,
“Normally Closed”}
BACnet Object Identier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Unsigned
BACnet Array[N] of
Character String
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Property Default Value Property Data Type Access
Object Identier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
BV12
“External Input Status”
Binary Value
Inactive
{0,0,0,0}
Normal
No Fault Detected
FALSE
BACnet Object Identier
Character String
BACnet Object Type
BACnet Binary PV
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Read
Read
Read
Read
Read
Read
Read
Read/Write
Property Default Value Property Data Type Access
Object Identier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Units
Max Pres Value
Min Pres Value
PIV3
“Damping Time”
Positive Integer Value
0
{0,0,0,0}
Normal
No Fault Detected
FALSE
Mode Specic
30
0
BACnet Object Identier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
BACnet Engineering Units
Real
Real
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Read