Tablo 4 Technical and Functional Specifications
Timing
Pre purge time:
0 sec
Waiting time:
0 sec
Pre ignition time:
2 sec
Safety time:
7 sec
Number of retrials: 5
Flame failure response time:
1 sec
Post ignition time:
0,4 sec
Post purge time:
0,8 sec
Pump over-run time:
A) for DHW
- Monothermic&Winter mode
- Monothermic&Summer mode&3 way electric valve
- Bithermic& Winter mode
- Bithermic& Summer mode
B) for CH
- Winter mode
- Summer mode
3 sec
5 sec
3 sec
T
CH > 75 °C: 1 sec
TCH < 75 °C: 0 sec
10 min
5 sec
Pump anti-seize run time:
A) Bithermic type
B) Monothermic type
5 sec
5 sec
CH anti-cycling time:
3 min (
0 min … 15 min)
TTB error waiting time:
15 min
Chimney sweep run time:
20 min
Timing tolerance: ± 5%