1. Application
2. Technical data
Electronic timer e.control.t08m (hereinafter referred to as timer) is used for realization of time functions in the control systems and automati-
on. It operates according to the set time schedule planned by the user.
The timer meets requirements of EN 60730-1, EN 60730-2-7.
The product must be operated under the following environmental conditions:
• non-explosive;
• does not contain corrosive gases and vapors in concentrations destroying metals and insulation;
• not rich conductive dust and vapors;
• lack of direct exposure to ultraviolet radiation;
• should not be significant shock or vibration.
Transportation and storage are only permitted in the original packaging.
See Pic. 1.
See Pic. 4.
At the first inclusion or reset, timer can be setting with buttons «▲▼» and «OK».
See Pic. 5.
See Pic. 6.
See Pic. 7.
If there is no activity for 1 minute, the timer will automatically exit from the menu.
Table 1
Electronic timer e.control.t08m
User’s guide and manual operation
EN
Parameter name Value
Supply terminals A1-A2
Rated voltage, V AC/DC 24-264
Power consumption, W 1
Supply voltage tolerance, % ±10
Number of channels single channel
Number of programs 80
Program weekly program, daily program
Operation modes manual, automatic, holiday
Summer/winter times off, automatic changes
Time tolerance, °C <1 s/day at 25
Power reserve, years 10
Data readout LCD display
Number of contacts 1 C/O
Current of contacts, A (for AC-1) 16
Switching capacity, VA (for AC-1) 4 000
Mechanical life 10
6
Electrical life 10
5
Rated insulation voltage, V 250
Protection degree IP20
Pollution degree 3
Altitude, m 2 000
Ambient temperature, °C -20…+55
Permissible relative humidity, % <50 (40 °C, without condensation)
Storage temperature, °C -30…+70
Wire size, mm
2
1…4
Tightening torque, Nm
0,5
Dimensions, mm
90×36×64
3. Wiring diagram
First settings
Main menu
Time setting
Date setting
4. Installation and operating
The timer is installed in a plastic or metal box on a standard DIN-rail width 35 mm with latches having two fixed positions.
• Connect the power supply: L (+) to terminal A1, N (-) to terminal A2. Output normally open timer contact (terminal 18 – NO, 16 - NC 15 - com-
mon) is connected to the phase conductor breaking load power or break the conductor actuator power switching device, such as a contactor coil.
1 Press «MENU» key to enter main menu.
2 With «▲▼» buttons select the desired item.
1 Select «DATE» and press «OK» key.
2 Select adequate hour with «▲▼» keys and press «OK» key.
3 Select adequate minute with «▲▼» keys and press «OK» key.
4 Exit from the setting by pressing «MENU» key.
1 Select «DATE» and press «OK» key.
2 Select adequate year with «▲▼» keys and press «OK» key.
3 Select adequate month with «▲▼» keys and press «OK» key.
4 Select adequate day with «▲▼» keys and press «OK» key.
5 Exit from the setting by pressing «MENU» key.
Question and Answer IconNeed help?

Do you have a question about the E.NEXT E.CONTROL.T08M and is the answer not in the manual?

Overview

The e.control.t08m electronic timer is designed for implementing time functions within control and automation systems, operating according to a user-defined time schedule. It complies with EN 60730-1 and EN 60730-2-7 standards.

Technical Specifications

The timer operates with a supply voltage of AC/DC 24-264V, consuming 1W of power. It tolerates a supply voltage deviation of ±10%. It features a single channel and can store up to 80 programs. Programming options include weekly and daily programs, with operation modes such as manual, automatic, and holiday. It also supports automatic changes for summer/winter time. The time accuracy is less than 1 second per day at 25°C, and it has a power reserve of 10 years, ensuring data retention during power outages.

Data is displayed on an LCD. The timer is equipped with one changeover (C/O) contact, rated for 16A (AC-1) and a switching capacity of 4000VA (AC-1). Its mechanical life is 10^6 cycles, and its electrical life is 10^5 cycles. The rated insulation voltage is 250V. It has an IP20 protection degree and a pollution degree of 3. It can operate at altitudes up to 2000m.

The ambient temperature range for operation is -20°C to +55°C, with a permissible relative humidity of less than 50% (at 40°C, without condensation). Storage temperature ranges from -30°C to +70°C. The timer accepts wire sizes from 1 to 4 mm² with a tightening torque of 0.5 Nm. Its dimensions are 90x36x64 mm.

Environmental Conditions

For proper operation, the timer must be used in non-explosive environments, free from corrosive gases and vapors that could damage metals and insulation, and not exposed to conductive dust or vapors. It should also be protected from direct exposure to ultraviolet radiation and significant shock or vibration. Transportation and storage are only permitted in the original packaging.

Installation and Operation

The timer is designed for installation in a plastic or metal box on a standard 35mm DIN-rail, secured with two-position latches. Power supply connections are made to terminals A1 (L+) and A2 (N-). The output contact (terminal 18 - normally open, 16 - normally closed, 15 - common) is connected in series with the phase conductor of the load power or the power switching device of an actuator, such as a contactor coil.

First Settings

Upon initial power-up or after a reset, the timer can be configured using the "▲▼" and "OK" buttons. This includes setting the language, date, and time.

To access the main menu, press the "MENU" key. Use the "▲▼" buttons to select the desired item. If there is no activity for 1 minute, the timer will automatically exit the menu.

Time and Date Setting

To set the time:

  1. Select "DATE" from the main menu and press "OK".
  2. Use "▲▼" keys to adjust the hour and press "OK".
  3. Use "▲▼" keys to adjust the minute and press "OK".
  4. Press "MENU" to exit.

To set the date:

  1. Select "DATE" from the main menu and press "OK".
  2. Use "▲▼" keys to adjust the year and press "OK".
  3. Use "▲▼" keys to adjust the month and press "OK".
  4. Use "▲▼" keys to adjust the day and press "OK".
  5. Press "MENU" to exit.

Language Setting

  1. Select "LANGUAGE" and press "OK".
  2. Use "▲▼" keys to select the desired language and press "OK".
  3. Press "MENU" to exit.

Summer/Winter Time Setting

  1. Select "SU-WI" and press "OK".
  2. Use "▲▼" keys to select the desired summer/winter mode and press "OK".
  3. Set the start month and day for summer time, pressing "OK" after each.
  4. Set the start month and day for winter time, pressing "OK" after each.
  5. Press "MENU" to exit.

Holiday Mode

  1. Select "HOLIDAY" and press "OK".
  2. Select "ON" to activate holiday mode and press "OK".
  3. Set the start year, month, and day of the holiday, pressing "OK" after each.
  4. Set the end year, month, and day of the holiday, pressing "OK" after each.
  5. Return to the "HOLIDAY" menu. Press "MENU" to exit.
  6. Alternatively, select "OFF" to deactivate holiday mode and press "OK", then press "MENU" to exit.

Program Management

Creating a New Program:

  1. Select "PROGRAM" and press "OK".
  2. Select "NEW" and press "OK". The device will briefly display free memory spaces and the new program number. If memory is full, "FULL" will appear.
  3. Select "ON/OFF" mode or "PULSE" mode.
  4. For ON/OFF, select "OUT-ON" or "OUT-OFF" using "▲▼" keys and press "OK".
  5. Set the hour and minute using "▲▼" keys and press "OK" after each.
  6. Set the program activity for each weekday (Monday to Sunday) using "▲▼" keys. "YES" enables the program for the flashing day, "NO" disables it.
  7. For PULSE mode, set the pulse duration (1-99 seconds).
  8. Return to the last menu by pressing "MENU". Long press "▲" or "▼" for 0.5 seconds to rapidly increase or decrease numerical values.

Modifying a Program:

  1. Select "PROGRAM" and press "OK".
  2. Select "REVIEW" and press "OK".
  3. Use "▲▼" keys to select the desired program and press "OK".
  4. For ON/OFF programs, display the output state and select "OUT-ON" or "OUT-OFF" using "▲▼" keys, then press "OK".
  5. For Pulse programs, display the output state and press "OK".
  6. Set the hour and minute using "▲▼" keys and press "OK" after each.
  7. Set the program activity for each weekday using "▲▼" keys. "YES" enables the program, "NO" disables it.
  8. For Pulse programs, set the pulse duration (1-99 seconds).
  9. Return to the last menu by pressing "MENU".

Reviewing Programs:

  1. Select "PROGRAM" and press "OK".
  2. Select "REVIEW" and press "OK".
  3. Use "▲▼" keys to view the set programs and press "OK".
  4. Press "MENU" to exit.

Deleting a Program:

  1. Select "PROGRAM" and press "OK".
  2. Select "DELETE" and press "OK".
  3. To delete a single program: Select "SINGLE" and press "OK". Use "▲▼" keys to select the program, then "▲▼" keys to select "YES" or "NO" and press "OK". Return to the "SINGLE" sub-menu, then press "MENU" to exit.
  4. To delete all programs: Select "ALL" and press "OK". Use "▲▼" keys to select "YES" or "NO" and press "OK". Return to the "DELETE" sub-menu, then press "MENU" to exit.

Reset

Pressing the three keys simultaneously for 3 seconds will reset the device to factory settings. The device will be restored to factory settings. During this process, the output contact 18-15 will be closed. If the output states of other operation modes were changed, "MANUAL" mode exits automatically.

Safety Requirements

The device should only be installed, operated, and maintained by qualified personnel. Do not attempt to repair the device yourself; otherwise, no responsibility is assumed by the manufacturer or seller. Do not open or disassemble the device. Never use the product in environments with corrosive gases, strong sunlight, or rain.

Utilization

The timer should be disposed of by transferring the product to a specialized enterprise for recycling in accordance with the requirements of the legislation in the territory of sale.

Warranty

The average lifespan of the device is 5 years, subject to installation, operation, ambient conditions, transportation, and storage requirements. The warranty period is 1 year from the date of purchase, subject to the same conditions. The warranty does not cover products with mechanical damage, damage resulting from improper transportation, storage, assembly, or operation, or damage from independent, tampered, or repaired products. Non-compliance with these instructions invalidates the warranty. No modifications or alterations to the devices are permitted. For technical support during the warranty period, visit www.enext.com.

E.NEXT E.CONTROL.T08M Specifications

General IconGeneral
BrandE.NEXT
ModelE.CONTROL.T08M
CategoryTimer
LanguageEnglish