Catalog data MN650002EN
Effective February 2019
Deadbreak apparatus connectors
By hand, turning clockwise, thread insulating plug in as
far as possible.
Using a torque wrench and 1" socket complete threading
clockwise until tight. Torque to 55 ft-lbs. See Figure 28.
Step 15.
Check tightness of termination
Check tightness by hand by moving T-body forward and
back (perpendicular to the apparatus frontplate). Do not
move side to side as this may loosen the connection.
If tight:
Re-torque to 55 ft-lbs.
If loose:
Remove insulating plug and T-body from apparatus
bushing.
Inspect threads of the stud and insulating plug for
damage.
If damaged, replace damaged component and re-install
per previous installation instructions.
If no damage is found, re-install per previous
installation instructions.
Step 16.
Cap the insulating plug
Clean and lubricate inner surface of insulating plug cap
with lubricant supplied.
Attach hotstick onto cap ring.
Push cap onto insulating plug until it snaps into place.
Refer to Figure 29.
Step 17.
Ground system
Connect one concentric neutral wire to drain wire tab of
the T-body or use a separate uninsulated copper wire
(#14 AWG/1.6 mm). Refer to Figure 30.
Twist to bundle all concentric neutral wires and connect
to common ground point. Provide sufficient slack to allow
T-body movement to standoff bushing.
Figure 30. Illustration of the drainwire.
T-body
Drain wire
Concentric neutral
wires
Figure 29. Line illustration of installing the insulating
plug cap.
Concentric neutral wires
T-body
Insulating plug cap
Figure 28. Line illustration of tightening termination.
Apparatus
bushing
Concentric
neutral wires
Dimension "a" (detail)
approx. 1/8" (3.18 mm)
Torque
wrench
Complete threading
1" Socket
14
600 A 35 kV class BOL-T connector assembly installation instructions for MN650002EN February 2019

Other manuals for Eaton 600 A 15 kV class push-OP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 600 A 15 kV class push-OP and is the answer not in the manual?

Eaton 600 A 15 kV class push-OP Specifications

General IconGeneral
BrandEaton
Model600 A 15 kV class push-OP
CategoryCables and connectors
LanguageEnglish

Related product manuals