Table10. Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read To Write To Reset Low High
128 Minimum Percent
Regulation
XX.X %
MM-DD-YYYY HH:MM:SS
% View NA Operate Reset* NA NA
•This is the highest percentage that the regulator has lowered the input voltage since last
reset.
•The control requires an input voltage from a differential or source potential transformer
to obtain this parameter. Lack of this voltage will result in the parameter displaying
dashes.
130 Phase Angle
XXX.X Degrees
Degrees View NA NA NA NA NA
•The instantaneous metering display of the angle by which the sine curve of the voltage in
a circuit element leads or lags the sine curve of the current.
131 Load Current
Real
XXXX.X Amps
Amps View NA NA NA NA NA
•The instantaneous metering display of the real portion of the load current.
131 Load Current
Reactive
XXXX.X Amps
Amps View NA NA NA NA NA
•The instantaneous metering display of the reactive portion of the load current.
•The instantaneous metering display of the averaged secondary load voltage when in multi-
phase operation.
132 Average Source
Volt. Secondary
XXX.X Volts
Volts View NA NA NA NA NA
•The instantaneous metering display of the averaged secondary source voltage when in multi-
phase operation.
132 Average Comp
Volt. Secondary
XXX.X Volts
Volts View NA NA NA NA NA
•The instantaneous metering display of the averaged secondary compensated voltage for all
phases when in multi-phase operation.
132 Average Load
Current Primary
XXX.X Volts
Amps View NA NA NA NA NA
•The instantaneous metering display of the averaged primary load current when in multi-
phase operation.
132 Average Present
Tap Position
XX
--- View NA NA NA NA NA
•The instantaneous metering display of the average present tap position for all phases when
in multi-phase operation.
132 Average Maximum
Tap Position
XX
MM-DD-YYYY HH:MM:SS
--- View NA NA NA NA NA
•The instantaneous metering display of the average present tap position for all phases when
in multi-phase operation.
•This is reset to zero by pressing ENTER and then ENTER again to confirm.
74
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225003EN April 2018
CL-7 Voltage Regulator Control

Table of Contents

Other manuals for Eaton 600 A 15 kV class push-OP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 600 A 15 kV class push-OP and is the answer not in the manual?

Eaton 600 A 15 kV class push-OP Specifications

General IconGeneral
BrandEaton
Model600 A 15 kV class push-OP
CategoryCables and connectors
LanguageEnglish

Related product manuals