TABLE 5-3. Function Codes (continued)
Func.
Code
Level 1
Main Menu
Level 2
Sub-Menu
Level 3
Parameter
Security Level Factory
Setting
Key Entry Limit
Read Edit Reset Low High
25
Metering Forward
Demand
025 Forward
kW Load Present
XXXX.X kW
0 NA NA NA NA NA
This is the present value of the load kW, as a demand value, according to the demand time interval at FC 46.
26 Metering Forward
Demand
026 Forward
kvar Load High
XXXX.X kvar
(Date / Time shown)
0 NA 1 NA NA NA
This is the highest value of the load kvar (since last reset), as a demand value, according to the demand time interval at
FC 46.
Date and time of when the lowest value occurred is displayed.
26
Metering Forward
Demand
026 Forward
kvar Load Low
XXXX.X kvar
(Date / Time shown)
0 NA 1 NA NA NA
This is the lowest value of the load kvar (since last reset), as a demand value, according to the demand time interval at
FC 46.
Date and time of the occurrence of the lowest kvar load displayed.
26
Metering Forward
Demand
026 Forward
kvar Load Present
XXX.X kvar
0 NA NA NA NA NA
This is the present value of the load kvar, as a demand value, according to the demand time interval at FC 46.
27 Metering Forward
Demand
027 Maximum Tap
Position
XX
(Date / Time shown)
0 NA 1 NA NA NA
This is the highest tap position that the regulator has reached since last reset.
The maximum position and associated date and time can be reset via the reset key or via master reset, FC 38. This
parameter is not reset by the drag-hand reset switch.
Date and time of the occurrence of the maximum tap position is displayed.
28 Metering Forward
Demand
028 Minimum Tap
Position
XX
(Date / Time shown)
0 NA 1 NA NA NA
This is the lowest tap position that the regulator has reached (since last reset).
The minimum position and associated date and time can be reset via the reset key or via master reset, FC 38. This parameter
is not reset by the drag-hand reset switch.
Date and time of the occurrence of the minimum tap position is displayed.
43
CL-6 SERIES CONTROL INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225016EN January 2016

Table of Contents

Other manuals for Eaton 600 A 25 kV class PUSH-OP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 600 A 25 kV class PUSH-OP and is the answer not in the manual?

Eaton 600 A 25 kV class PUSH-OP Specifications

General IconGeneral
BrandEaton
Model600 A 25 kV class PUSH-OP
CategoryCables and connectors
LanguageEnglish

Related product manuals