Page 1
9EEBM240 WIRING CONNECTION
Warning
Please read the UPS user manual before installing the EBM
It is possible to connect more than one EBM in order to achieve any level of autonomy without mains power. Connect any Battery
Boxes in a cascade as shown in the figure below:
1. CONNECTION: Use 3 cables with 10 mm
2
section (Earth, +, N and -)
2. Connect the wires to the relative terminals, following exactly the instructions given below:
For 9E15Ki, 9E15KiXL, 9E20Ki, 9E20KiXL
(Must connect Two EBMs as a group)
a - Make sure that the fuse holder of the external battery box is open.
b - Connect the earth (PE) wire to EBM’s earth (PE) screw
c - Connect the positive (+) branch wire to 1
st
EBMs positive (+) terminal.
d - Connect the neutral (N) wire to 1
st
EBM negative (-) terminal and 2
nd
group EBM positive(+) terminal.
e - Connect the negative (-) branch wire to 2
nd
EBMs negative (-) terminal.
The suggested tighten force is 1.6Nm.