Storage
Transformers that will not be placed in service immediately 
should be stored with terminal compartment doors closed 
and sealed to prevent damage to bushings or other 
attachments.
Quality standards
ISO 9001 certified quality management system
Installation
Installation location
The transformer must be located to meet applicable fire 
codes. For indoor installations, the installation location must 
meet the requirements of the National Electrical Code 
(NEC
®
) with sufficient space requirements and proper over-
current protection as specified by the listing body that has 
jurisdiction over the installation.
These pad-mounted transformers are built to operate 
at altitudes up to 3300 feet at 30 °C average and 40 °C 
maximum ambient, unless otherwise specified. Before 
operating a standard transformer at higher altitudes, contact 
your Eaton representative. 
Mounting the transformer
The transformer should be mounted on a level concrete 
pad. The pad should be strong enough to support the 
weight of the transformer. The site must be adequately 
prepared to prevent the transformer from tilting beyond two 
degrees from horizontal.
Tilting beyond two degrees may cause internal components 
to come out of the oil and/or cables to mechanically stress 
the bushings and bushing gaskets. Excessive tilt (beyond 
two degrees) can result in a lower dielectric strength for the 
transformer than the basic insulation level (BIL) listed on the 
nameplate. Reduced BIL can result in an internal dielectric 
breakdown with a risk of explosion, tank rupture, or fire.
To maintain full cabinet security, the transformer tank and 
cabinet base have provisions for installing cleats to secure 
transformer to pad. If gaps still exist between the cabinet 
and pad after cleating the cabinet, the installation will not 
provide the security needed to prevent tampering by the 
public. Add a permanent mortar seal to fill the gaps.
Pre-service inspection (exterior)
New transformers, or transformers which are being 
activated after a period of storage, should be thoroughly 
inspected before being connected to the power distribution 
system to identify damage which may have occurred during 
storage.
1.   The transformer exterior should be inspected for nicks, 
dents, and scratches. Repair damage to weather-
resistant finishes promptly.
2.  The tank cover and manhole/handhole cover seals 
and all gaskets or seals at bushings, gauges, fuses, 
operating devices, etc., should be inspected for 
evidence of insulating liquid seepage. Repair leaking 
or improperly tightened gaskets and seals before the 
transformer is placed in service.
3.  Under normal conditions, the transformer leaves the 
factory with a slight positive pressure in the tank 
over the oil. However, due to changes in atmospheric 
conditions, the unit may arrive under vacuum (negative 
pressure). This is itself is not cause for concern, however 
continued absence of either negative or positive 
pressure may indicate a leak at a gasket seal or tank 
seam, and require further investigation. To leak test 
transformer, remove the pressure relief valve (see Figure 
1) and pressurize the headspace to ensure that there are 
no leaks. The test pressure should not exceed 7 psig. 
The established pressure should be maintained for at 
least four hours to ensure that all the seals are proper.
Figure 1.  Pressure relief valve.
WARNING 
Fire Hazard. Non-level installation of transformer 
can result in fire and cause severe personal injury or 
death. Prepare transformer installation site such that 
transformer does not tilt more than two (2.0) degrees 
from horizontal while the transformer is in service at 
the site.
2 Three-phase pad-mounted compartmental type installation and maintenance instructions   MN202001EN   August 2015