CL-7 control in Eaton control box, dead front
Table 1.  Kit parts identification
Item Description Part Number Qty
1 Jumper, 7 terminals width A613078004 1
2 Backpanel tool, plastic* A613098002 1
*Retain for future use.
ote:N Eaton‘s Universal PRA kit may include parts not 
required for every installation. Only parts required for 
this installation are included in this list.
Required tools
 
Screwdriver (Phillips)
 
Backpanel tool (included in kit)
ote:N Verify all kit items are present before beginning 
installation procedure.
Installation procedure
Follow these instructions to install the CL-7 control in a 
control box on an Eaton‘s Cooper Power series voltage 
regulator with a dead-front backpanel.
1.   Remove the existing control:
 
Refer to the appropriate voltage regulator control 
manual for complete instructions on removing a 
control.
 
Refer to document MN225016EN, VR-32 Voltage 
Regulators CL-6 Series Control Installation, Operation, 
and Maintenance Instructions for information on the 
Eaton‘s Cooper Power series CL-6 series voltage 
regulator control.
2.  For control boxes with an existing CL-6B regulator 
control, use a screwdriver to remove the latching 
bracket from the control box mounting tabs. Refer to 
Figure 1.
Figure 1.  Control box bracket removal
3.  In control boxes with a full back panel, locate the 
TB8 terminal board and use the back panel tool to 
remove the jumper between terminal 4 and 5. Refer 
to Figure 2. This step is not required for the short back 
panel.
Figure 2.  Removing jumper from TB8
4.  Identify the terminal board containing the control plug 
receptacle on the lower back panel. Peel back the strip 
containing the terminal markings in the center of this 
terminal board using the back-panel tool to reveal the 
terminal board jumpers. See Figure 3.
2
CL-7 Control Panel Retrofit
InstallatIon InstructIons   MN225018EN   April 2018