4
Replacement of Cover Gasket for Padmount Switchgear Side-Hinge-2 Models
FIELD SERVICE INSTRUCTIONS   MN285009EN   April 2019
1.4  Pull the pressure-relief valve to relieve pressure 
(Figure 17).
Record whether pressure was present or not.
Figure 17.   
1.5  Verify that the Gasket Replacement Kit contains the 
correct gaskets:
1.5.1   Remove the flat gaskets from the Gasket 
Replacement Kit.
1.5.2   Before removing the cover, pre-position the 
gaskets on the cover. Verify that the gaskets 
are the correct length and that all gasket holes 
align with the cover bolts.
If the gasket length, hole spacing, or 
number of holes does not match the cover, 
STOP. Do not proceed any further with the 
repair. Consult factory service.
1.5.3   Assemble the four gaskets at the puzzle 
dove-tail corner joints (Figure 18) to ensure the 
correct positioning of gaskets.
ote:N At the bolt holes, notice that the larger 
portion of the rubber is towards the 
interior of the tank.
Figure 18.   Dove-tail joint
2.  Perform the Switchgear Apparatus 
Functional Test
ote:N Consult factory service if the apparatus does 
not perform as expected during the functional 
test.
2.1  Prepare the switchgear apparatus for the test:
 
For units without an optional motor operator: 
Follow the procedure in step 2.1.1.
 
For units with an optional motor operator: 
Follow the procedure in step 2.1.2.
2.1.1   For units without an optional motor 
operator:
Manually open and close each single or three-
phase handle for all Source and Tap Ways.
Leave each handle in the Closed position.
2.1.2   For units with an optional motor operator:
a.  Electrically operate the handle to the 
Open position (Figure 19 - pre 2018 units; 
Figure 20  - 2018 & later units).
b.  Remove the drive pin connecting the 
motor operator to the handle drive lever 
assembly (Figure 21 & Figure 22); then 
allow the motor operator to drop away 
from the handle (Figure 23).
c.  Manually close, open, and then close each 
single or three-phase handle for all Source 
and Tap Ways.
Leave each handle in the Closed position.
Figure 19.   Handle at Open position (pre 2018 units)