Instructions for the FP-6000 Protective Relay
Table 4. Minimum List of Functions Which MUST be Programmed (continued).
SETTING DEFAULT SETTING INCR DISPLAY USER SETTING
IX Overcurrent
51 IX TOC Shape: XTRM List IT, I2T, I4T, FLAT, MOD, VERY, XTRM, IECA, IECB, IECC
51 IX TOC Reset: Calc List Inst, Calc, T Delay
51 IX TOC Direction: Both List Forward, Reverse, Both
51 IX TOC Pickup: 0.50 0.01 0.02 to 4.0
pu
or Disable
51 IX TOC Time Mult: 1.00 0.01 0.05 to 10.0
50X-1 IX IOC 1 Pickup: 1.00 0.01 0.1 to 20.0
pu
or Disable
50X-1 IX IOC 1 Delay (c): 60 1 0 to 9999 cycles
50X-1 IX IOC 1 Direction: Both List Forward, Reverse, Both
50X-1 IX IOC 2 Pickup: 2.00 0.01 0.1 to 20.0
pu
or Disable
50X-1 IX IOC 2 Delay (c): 6.00 1.00 0 to 9999 cycles
50X-1 IX IOC 2 Direction: Both List Forward, Reverse, Both
IR Residual Overcurrent
51R IR TOC Shape: XTRM List IT, I2T, I4T, FLAT, MOD, VERY, XTRM, IECA, IECB, IECC
51R IR TOC Reset: Calc List Inst, Calc, T Delay
51R IR TOC Direction: Both List Forward, Reverse, Both
51R IR TOC Pickup: 0.50 0.01 0.02 to 4.0
pu
or Disable
51R IR TOC Time Mult: 1.00 0.01 0.05 to 10.0
50R-1 IR IOC 1 Pickup: 1.00 0.01 0.1 to 20.0
pu
or Disable
50R-1 IR IOC 1 Delay (c): 60 1 0 to 9999 cycles
50R-1 IR IOC 1 Direction: Both List Forward, Reverse, Both
50R-1 IR IOC 2 Pickup: 2.00 0.01 0.1 to 20.0
pu
or Disable
50R-1 IR IOC 2 Delay (c): 600 1 0 to 9999 cycles
50R-1 IR IOC 2 Direction: Both List Forward, Reverse, Both
Unbal Alarm
46-2 I Unbal Alarm Threshold: 0.1 0.01 0.1 to 20.0
pu
, disable
46-2 I Unbal Alarm % (I2/I1): 40 1 2 to 40 percent
46-2 I Unbal Alarm Delay (c): 60 1 0 to 9999 cycles
47-2 V Unbal Alarm Threshold: 50 1 1 to 100 Volts, disable
47-2 V Unbal Alarm % (V2/V1): 40 1 2 to 40 percent
47-2 V Unbal Alarm Delay (c): 60 1 0 to 9999 cycles