6
Insulated case circuit breakers - pop-out
trip indicators
EATON www.eaton.com
Instruction Leaflet IL0131126EN
Effective January 2019
Figure 16. Step 7.
Step 8: Once the trip indicator is released from its mounting notch,
the trip indicator can be completely removed by pushing it up and out
of the mounting slot.
Step 9: To install a new pop-out trip indicator, follow Steps 3 through 9
of Section 2.
Section 4: Accessory secondary
connections
CAUTION
IDENTIFICATION WIRE NUMBERS MUST MATCH THE IDENTIFICATION
NUMBERS ON THE SECONDARY BLOCK/PLATE.
General information
1. Some electrical accessory leads are tagged with numbers associated
with the applicable connection diagram located in instruction
book TD013001EN. Leads are also supplied with keyed secondary
connector plugs to ensure proper connections (Figure 17). If the trip
indicator leads are not labeled, pre-printed labels are provided in the
trip indicator kit.
2. Secondary connections are made by plugging the connector plugs
into the appropriate location with a matching number label. A
connector plug already connected can be removed by squeezing
two release tabs together with small needle nose pliers and pulling
out (Figure 17).
Figure 17. Leads and connectors.
Figure 18. Connector plug removal.
Fixed breaker connections
Proceed with the following five steps:
Step 1: Become familiar with the fixed terminal block DIN rail type
mounting plate where secondary connections are made.
ote:N Secondary connection points have numerical and descriptive laser-etched
identifications.
Tagged
leads
Keyed
connector
Release
tabs