3
Instruction Leaflet IL0131126EN
Effective January 2019
Insulated case circuit breakers - pop-out trip
indicators
EATON www.eaton.com
Figure 4.
Red plunger
Remote reset interlock indicator shown.
Section 2: Installation of pop-out trip
indicator
Proceed with the following nine steps.
Step 1: Remove the four screws holding the front cover in place (two
on each side of the cover).
Figure 5. Step 1.
Step 2: Remove the front cover. Pull down on the charging handle to
simplify removal.
Figure 6. Step 2.
Step 3: Remove the plug in the breaker cover. This will allow the red
plunger to pass through the cover.
Figure 7.
Plug
Step 3.
Step 4: Slide the left accessory tray (used for mounting accessories
such as ST, UVR, and OTS) approximately 1 in. (25.4mm) to the left
by depressing the thumb tab and sliding the tray out. This will create
sufficient room to install the trip indicator.
Table 1. Remote reset ratings
Control voltage Frequency Operational voltage (range 70–110%) Inrush power consumption (VA) Reset closing time (ms)
24 DC 17–26 500 25
110–127 50–60 Hz 77–140 540 25
110–125 DC 77–138 540 25
208–240 50–60 Hz 146–264 500 25
220–250 DC 154–275 515 25