Cabinet dimensions
Instruction manual IM1002004E September 2015 www.powerquality.eaton.com
Cabinet dimensions
Table 6. Power-Sure 700 unit cabinet sizes
kVA
rating Bypass Metering
Cabinet size
H x W x D (in) BTUs/Hr Weight (Lb)
10 Yes No 30.2 x 22.2 x 29.0 1,025 440
10 Yes Yes 44.2 x 22.2 x 29.0 1,205 520
15 Yes No 30.2 x 22.2 x 29.0 1,540 465
15 Yes Yes 44.2 x 22.2 x 29.0 1,540 700
25 Yes Yes 44.2 x 22.2 x 29.0 2,560 700
30 Yes Yes 44.2 x 22.2 x 29.0 3,090 720
45 Yes Yes 44.3 x 45.9 x 29.0 4,600 950
50 Yes Yes 66.0 x 29.0 x 35.5 7,332 1,176
75 Yes Yes 76.0 x 34.4 x 35.5 9,514 1,575
100 Yes Yes 76.0 x 34.4 x 35.5 11,833 2,014
125 Yes Yes 76.0 x 34.4 x 35.5 14,748 2,137
150 Yes Yes 76.0 x 34.4 x 35.5 17,698 2,240
225 Yes Yes 77.4 x 56.0 x 41.5 23,000 3,300
300 Yes Yes 77.4 x 56.0 x 41.5 30,750 4,000
500 Yes Yes 77.0 x 72.4 x 48.4 51,250 5,500
Manual bypass switch
The manual bypass switch is a break-before-make switch
located on the Power-Sure 700. The manual bypass switch
is used to bypass all power electronics in case of failure.
Bypass is standard on 50 kVA and larger units and an option
on 45 kVA and smaller units.
ote:N This switch may be added in the field.
Normal mode
With the switch in the normal position, the Power-Sure 700
will provide clean and regulated power to the critical loads.
The Power-Sure 700 should have the switch in the normal
position unless a failure has occurred.