Operation
Instruction manual IM1002004E September 2015 www.powerquality.eaton.com
Operation
The Power-Sure 700 is operated by simply turning on the
main AC input circuit breaker. All units 50 kVA and larger are
equipped with a bypass switch as a standard feature. For
units 45 kVA and smaller, the bypass switch is optional. This
is a no load switch and MUST only be operated when the
unit is OFF. The bypass switch should be in the “NORMAL
position unless a problem occurs with the system. If a
problem occurs, turn OFF the main AC circuit breaker
and turn the bypass switch to the “BYPASS” position.
Re-energize the system by turning on the AC circuit breaker
and contact the Customer Support Department for repairs.
Any ALERT” condition requires the main AC input breaker
to be turned off in order to reset the ALERT” light.
FOR ASSISTANCE, CALL 1-800-809-2772, option 4, and
then option 2.
Bene ts of owning and using the
Power-Sure 700
Line harmonic filtering
Small physical size
Simple and inexpensive installation
Highly efficient
Quiet operation
Low BTU output
Low failure rate
Seven-tap, microprocessor control and diagnostics
UL
®
Listed to 1012 standards
Priced to be affordable
Conservatively rated
Extremely high surge capability
Simple operation
Input electronic circuit breakers
Nationwide customer support service
Speci cations
Dynamic electrical specifications
Output: maintained to within ±3% of nominal
a
Input: +10% to –23% of the nominal rated input
ab
Frequency: 60 Hz ±3 Hz
a
Input power factor: >0.99 PF with resistive load
Line regulation: output is ±3% of nominal for input
variations of +10% to –23% of nominal
Load regulation: output maintained within 3% from no
load to full load
Response time: <1/2 cycle
Correction time: output will correct to within ±3% of
nominal in 1.5 cycles or less
Harmonic distortion: Less than 1.0% THD added to
the output waveform under any dynamic linear loading
conditions presented to the line regulator
Transverse-mode noise attenuation: 3 dB down at 1000 Hz,
40 dB/decade to below 50 dB with resistive load
Common-mode noise attenuation: 146 dB
Audible noise: 45 dB or less
Turn on characteristics: when energized, voltage
overshoot will be less than 5% of nominal for 1 cycle
or less
Overload rating: 1000% for 1 cycle and 200% for
10 seconds
Ambient rating: –10º to +40º Celsius
Integral manual rotary maintenance bypass switch
standard on 50 to 500 kVA units and optional on
smaller units
ote: N 50 Hz models available.
Figure 1. Regulation graphs
a
Optional extended input regulation range provided on some units.
If provided, reference the description next to the units specification tag.
b
Between 160 V and 229 V at 208 V nominal. Between 369 V and 528 V
at 480 V nominal.