31
8 Health Monitor
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN March 2019 www.eaton.com
8.3 Health Monitor Reset procedure
The counters in the Health monitor can be reset. The reset procedure can reset all health counters or subsets of counters. It
is highly recommended that the Health counters are only reset by someone with knowledge of the power system. Resetting
counters on a unit that has encountered multiple high power events could lead to false indication of breaker health.
8.3.1 Power Xpert Protection Manager (PXPM)
Go to Device Settings:
Reset Trip Unit::
Choose counters to reset: