40
10 Available protection settings
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN March 2019 www.eaton.com
10.2.11 PDC2 PXR25 and 20D settings
Frame 63 A 100 A 160 A 200 A 250 A All All 63 A 100 A 160 A 200 A 250 A G styles
Profile Long delay Short delay Instantaneous Ground
Setting Pickup Ir (amps) Time (s)
Pickup
(Isd)
Isd =nx (lr)
Time
(tsd)
tsd (s) Pickup li = nx (In)
Pickup (Ig)
lg = nx (In)
Time
(tg)
tg (s)
Min
16 25 40 50 63 0.5 1.5 0.050 2 2 2 2 2 0.2 0.100
Max
63 100 160 200 250 24 12.0 0.500 17.46 11.00 13.13 10.50 8.40 1.0 1.000
Min
0.5 0.067 0.2 0.067
Max
7 0.300 1.0 0.300
Step
1.00 1.00 1.00 1.00 1.00 0.10 0.10 0.01 0.10 0.10 0.10 0.10 0.10 0.01 0.01
Add'l opt
OFF OFF
I²t Flat Instantaneous override Trip Flat
I
4
t I
2
t 1100 A 2100 A Alarm I
2
t
10.2.12 PDG3 PXR10 settings (LI)
Frame 125 A 250 A 400 A H250 A H400 A H600 A All 125 A 250 A 400 A H250 A H400 A H600 A
Profile Long delay Instantaneous
Dial Ir (A) Ii (x In)
Setting
Pickup Ir (amps)
Time (s)
at 6x (Ir) Pickup Li = nx (In)
A
45 90 160 90 160 250 10 2 2 2 2 2 2
B
50 100 175 100 175 275 10 3 3 3 3 3 3
C
60 110 200 110 200 300 10 4 4 4 4 4 4
D
63 125 225 125 225 320 10 5 5 5 5 5 5
E
70 150 250 150 250 350 10 6 6 6 6 6 6
F
80 160 275 160 275 400 10 8 8 7 10 8 7
G
90 175 300 175 300 450 10 10 10 8 15 10 8
H
100 200 320 200 320 500 10 15 12 9 20 12 9
J
110 225 350 225 350 550 10 20 15 10 25 15 10
K
125 250 400 250 400 600 10 24.0 17.6 11 28.8 18 12.0
Instantaneous override
3000 A 4400 A 2100 A
10.2.13 PDG3 PXR10 settings (LSI)
Frame 125A 250A 400A H250 A H400 A H600 A All All 125 A 250 A 400 A H250 A H400 A H600 A
Profile Long delay Short delay Instantaneous
Dial Ir (A) SD profile Ii (x In)
Setting Pickup Ir (amps)
Time (s)
at 6x (Ir)
Pickup
(Isd)
Isd =nx (lr)
Time (tsd)
tsd (s) Pickup Li = nx (In)
A
45 90 160 90 160 250 10 2.0 0.15 0 2 2 2 2 2 2
B
50 100 175 100 175 275 10 2.0 0.300 3 3 3 3 3 3
C
60 110 200 110 200 300 10 2.0 I
2
t 4 4 4 4 4 4
D
63 125 225 125 225 320 10 4.0 0.150 5 5 5 5 5 5
E
70 150 250 150 250 350 10 4.0 I
2
t 6 6 6 6 6 6
F
80 160 275 160 275 400 10 6.0 0.150 8 8 7 10 8 7
G
90 175 300 175 300 450 10 6.0 0.300 10 10 8 15 10 8
H
100 200 320 200 320 500 10 10.0 0.150 15 12 9 20 12 9
J
110 225 350 225 350 550 10 2.0-10.0 0.05 to 0.30 20 15 10 25 15 10
K
125 250 400 250 400 600 10 OFF - 24.0 17.6 11 28.8 18 12.0
Configurable using PXPM software Instantaneous override
3000 A 4400 A 7200 A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Power Xpert PXR Series and is the answer not in the manual?

Eaton Power Xpert PXR Series Specifications

General IconGeneral
BrandEaton
ModelPower Xpert PXR Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals