DANGER
Hazardous voltage. Do not connect potential
transformer low-voltage secondaries to the control
through cables or other wiring until the unit is installed
in the field. Transformer high-voltage primary windings
will become live when 120/240V AC is applied to the
control from an alternate source if the transformer
secondary is connected. Failure to comply may result in
severe personal injury or death.
T371.2
WARNING
Hazardous voltage. Before applying power to the control,
confirm that male pins of the input power receptacle are
electrically insulated to prevent unintentional contact
with 120/240V AC voltage. Failure to do so may result in
severe personal injury or death.
T372.1
Figure 23. 120 or 240 VAC 2-wire with ground control power input with low voltage closing (shown with default
factory wiring connected to B-phase voltage metering with B-phase incoming supply)
30 OPERATION INSTRUCTIONS MN280049EN September 2017
Form 4D Microprocessor-based pole-mount recloser control installation and operation instructions

Table of Contents

Other manuals for Eaton Tandem ELF Current-Limiting Dropout Fuse

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Tandem ELF Current-Limiting Dropout Fuse and is the answer not in the manual?

Eaton Tandem ELF Current-Limiting Dropout Fuse Specifications

General IconGeneral
BrandEaton
ModelTandem ELF Current-Limiting Dropout Fuse
CategoryCables and connectors
LanguageEnglish

Related product manuals