EasyManua.ls Logo

Eaton xEffect - Page 6

Eaton xEffect
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2.2.1. – 3
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCdM
Description
Accessories:
Auxiliary switch for subsequent installation to the left Z-HK 248432
Tripping signal contact for subsequent installation to the right Z-NHK 248434
Automatic restarting device Z-FW/LP 248296
Z-FW-LPD 265244
Remote control Z-FW-MO 284730
Pre-mounted sets Z-FW-LP/MO 290171
Z-FW-LPD/MO 290172
Remote testing module Z-FW/003 248298
Z-FW/010 248299
Z-FW/030 248300
Sealing cover set Z-RC/AK-4TE 101062
Switching interlock IS/SPE-1TE 101911
• Residual current devices
• Shape compatible with and suitable for standard busbar connec-
tion to other devices of the xEffect-series
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Universal tripping signal switch, also suitable for FAZ, FRBmM-1N
can be mounted subsequently
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Tripping indicator white - blue
• Additional Safety
- possibility to seal
- possibility to lock in ON and OFF position
• Delayed types suitable for being used with standard fluorescent
tubes with or without electronical ballast (30mA-RCD: 30 units per
phase conductor, 100mA-RCD: 90 units per phase conductor).
Notes: Depending of the fluorescent lamp ballast manufacturer
partly more possible. Symmetrical allocation of the fluorescent
lamp ballasts on all phases favourably. Shifting references of the
fluorescent lamp ballast manufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suit-
able for “fault current/residual current protection” and “additional
protection” within the meaning of the applicable installation rules.
• Mains connection at either side
• The 4-pole device can also be used for 3-pole connection:
See connection possibilities.
• The 4-pole device can also be used for 2-pole connection:
See connection possibilities.
• The test key “T” must be pressed every year. The system operator
must be informed of this obligation and his responsibility in a way
that can be proven. The yearly test interval is only valid for residen-
tial and similar applications. Under all other conditions (e.g. damp -
ly or dusty environment), it's recommended to test in shorter inter-
vals (e.g. monthly). A test is further needed if red and yellow LED
are on together.
• Pressing the test key “T” serves the only purpose of function test-
ing the residual current device (RCD). This test does not make
earthing resistance measurement (R
E
), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Functioning
- The green LED becomes active at 0-30% I
Δn
- The yellow LED becomes active at 30-50% I
Δn
- The red LED becomes active at >50% I
Δn
• Potential-free relay (NO contact, in parallel with the yellow LED, up
to 1 A ohmic load / 230 V~) for external prewarning function.
Bistabile, means the warning stays on also when the breaker trips,
until reset.
Type -A: Protects against special forms of residual pulsating DC
which have have not been smoothed.
Type -G: High reliability against unwanted tripping. Compulsory
for any circuit where personal injury or damage to property may
occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
Type -G/A: Additionally protects against special forms of residual
pulsating DC which have not been smoothed.
Type -R: To aviod unwanted tripping due to X-ray devices.
Type -S: Selective residual current device sensitive to AC, type -S.
Compulsory for systems with surge arresters downstream of the
RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5).
Type -S/A: Additionally protects against special forms of residual
pulsating pulsating DC which have not been smoothed.
Type -U: Suitable for speed-controlled drives with frequency con-
verters in household, trade, and industry.
Unwanted tripping is avoided thanks to a tripping characteristic
designed particularly for frequency converters.
See also explanation “Frequency Converter-Proof RCDs - What for?”.
Application according to ÖVE/ÖNORM E 8001-1 and Decision
EN 219 (1989), VDE 0100, SEV 1000.

Related product manuals