EasyManua.ls Logo

Eco-King C99 - Page 32

Eco-King C99
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Part 5.1 Further Venting Options: PVC/CPVC/Polypro single pipe
REQUIREMENTS FOR INSTALLATION OF SINGLE PIPE VENTING ON ECO-KING BOILERS IN CANADA
Venting PART 1 Installations must be made with ANY vent pipe system certified to ULC-S636. Examples are, M&G
Duravent, Cox Geelen and Centrotherm polypropylene. They are approved vent manufacturers in Canada supplying
vent material listed to ULC-S636, but are not exclusive. Any PP manufacturer approved to ULC S-636 can be used.
Please see Table 1 below for an outline.
Table 1 Approved exhaust vent material on Eco-King Boilers
Material
Standards for installation in:
United States
Canada
Polypropylene
UL Listed
ULC-S636
Concentric venting
UL Listed
ULC-S636
**When transitioning to 2” venting, a 3” to 2” reducing adapter should be used**
NOTE: See Part 3 for PP vent instructions
NOTE: Eco-King Boilers have a high temp flue gas protection switch
Venting PART 2 Air intake must be brought into the boiler from outside, with one exception outlined in part 4 of this
addendum, see page 4. Approved materials for air intake are listed in Table 2 below:
Table 2 Approved air intake material for Eco-King Boilers
Material
Standards for installation in:
United States
Canada
Sheet Metal
Not applicable
Not applicable
ABS
UL Listed
Not applicable
PVC Cellular Foam Core
UL Listed
Not applicable
PVC DWV
ANSI / ASTM D2665
Not applicable
PVC Schedule 40 / 80
ANSI / ASTM D1785
ULC-S636
CPVC Schedule 40 / 80
ANSI / ASTM F441
ULC-S636
Polypropylene
UL Listed
ULC-S636
Concentric venting
UL Listed
ULC-S636
Venting PART 3 The use of single pipe Eco-King (M&G) polypropylene or any polypropylene venting rated to ULC
S-636 is now available to be used with Eco-King Boilers. No special adapter needed. Please review the following
instructions:
It is possible though to use a two pipe system (one for intake and one for exhaust) by following these steps:
1) A black O-ring seal (see figure 1) on the concentric air intake portion must be used to block air intake (see
figure 3). This black O ring is supplied with boiler. It is placed with the installation manuals in a plastic bag
2) Then the white cap on the separate single pipe air intake must be removed from the boiler (see figure 1)
3) Add the supplied O-Ring seal, which comes in a plastic bag with the install manuals (see figure 2)
4) Now the boiler is ready to be used in a two pipe system. Just connect any two 3” (80mm) polypropylene
fittings to the exhaust and intake. Look at Figure 4 to see how the two pipes system will look
32
O-Ring seal to cover air intake on
concentric opening. Insert where red
arrow points (see figure 3)
O ring seal for air intake when
using two pipes. To be placed
where red arrow points (see
figure 2)
Figure 1
Remove white cap to open
air intake inlet
Exhaust
Intake

Table of Contents