Essential checks before burner startup, covering gas, valves, seals, and electrical connections for safe operation.
Advice on securing adjustable parts and verifying flue combustion parameters (CO2, CO) post-adjustment.
Procedure to adjust the air pressure switch for optimal CO2 and CO levels, ensuring correct air flow.
Setting the gas pressure switch to 50% of the gas inlet pressure for proper regulation.
Adjusting the servomotor cams (Siemens SQN 75) for air damper control during ignition and operation.
Verifying the flame detection system using a microammeter to ensure reliable ignition and safety.
Diagram detailing the correct placement of ionization and ignition electrodes for reliable firing.
Illustrative guide showing the correct steps for mounting the burner unit onto the boiler.
Instructions and visual aids for safely disassembling the burner's internal tubes.
Routine annual checks of burner components, including combustion head and electrodes, by qualified personnel.
Essential checks for power, gas pressure, and control system connectivity before performing any maintenance.
Steps to diagnose and resolve issues when the burner fails to initiate operation.
Diagnosing and fixing burner lockouts occurring at the completion of an operating cycle.
Steps to identify and correct problems preventing the burner from igniting.
Resolving burner lockouts triggered by the safety time limit during startup.
Diagnosing burner lockouts that occur after a period of successful operation.