Pages
The connecti
o
n
diagram
of OP
-
DVP
-
CAB0
2 RXD
5 TXD
OP
s
id
e
3 TXD
4 RXD
PLC
s
id
e
9PIN
8PIN
5 GND
8 GND
Note: it is
normal
for all OP series
models
.
7
-
8
LG
Master
-
K series PLC
The
OP series can communicate with
LG
Master
-
K series PLC, the communication port is
port 2.
Item
Content
OP32
0
communication
port
9 pin communication port
PLC
communication
port
Port2
The default communication
parameter
9600 bps, 8 bit, 1 stop, Even
ID
1
Protocol
Modbus Slave ( RTU ( HEX ) )
Communication distance (the
farthest)
15 m
Communication
format
R
S232
The type of the cable
OP
-
LG
-
CAB0
The corresponding addresses of
the switch value
M000
-
M191F
The corresponding addresses of
the digital value
D0000
-
D4500